pump is overheated, but no heat transfer from the collector to the store, flow
and return have the same temperature; perhaps also bubbling in the lines.
air or gas bubbles in the system?
no
yes
Is the collector circuit blocked at
the dirt trap?
yes
Clean dirt trap
pump starts for a short moment, switches off, switches on again, etc.
temperature difference at the
controller too small?
no
yes
Wrong position of collector
sensors?
yes
Change
∆
ton and
∆
toff
correspondingly.
no
no
oK
pump starts up very late.
the temperature diffrence between store and collector increases enor-
mously during operation; the collector circuit cannot dissipate the heat.
Collector circuit pump
defective?
no
yes
Heat exchanger calcified?
yes
Check / replace it
Decalcify it
no
Heat exchanger blocked?
yes
no
Clean it
Heat exchanger too small?
yes
Change
∆
ton and
∆
toff correspondingly.
switch-on temperature diffe-
rence
∆
ton too large?
no
yes
Vent the system; increase the
system pressure to a static pri-
mary pressure of at least plus
0.5 bar (7.25 psi); if necessary
continue to increase pressure;
switch the pump off and on
for a short time.
plausibility control of
the option tube collec-
tor special function
mount the collector sensor at
solar flow (warmest collector
output); use immersion sleeve
of the respective collector.
replace with correctly
sized one.
non-ideal position of the
collector sensor (e.g. flatscrew
sensor instead of sensor in
immersion sleeves).
yes
activate tube collector
function if necessary.
o.k.