63
adjustment channel Description
adjustment range / selection Factory setting
Days of the week
Day selection
all days, monday ... sunday,
Continue
-
timer
time frame adjustment
00:00 ... 23:45
-
Correction
Correction
1 ... 20 K
5 K
relay
rtH relay selection
system dependent
system dependent
rtH
room thermostat
activ., Deactivated
Deactivated
afterheating
afterheating option
Yes, no
no
mode
afterheating mode
therm., Boiler
therm.
relay
afterheating relay selection
system dependent
system dependent
sensor 1
afterheating sensor 1 selection
system dependent
system dependent
sensor 2
afterheating sensor 2 selection
system dependent
system dependent
loading pump
loading pump option
Yes, no
no
relay
loading pump relay selection
system dependent
system dependent
overrun time
loading pump overrun time
0 ... 300 s
60 s
activ.
activation / Deactivation
activ., Deactivated
Deactivated
Δ
ton
switch-on temperature difference -15.0 ... +44.5 K
+5.0 K
Δ
toff
switch-off temperature difference -14.5 ... +45.0 K
+15.0 K
Function
Function activated / deactivated activ., Deactivated
Deactivated
Interval
mixer interval
1 ... 20 s
4 s
runtime
mixer runtime
10 ... 600 s
240 s
offset
automatic adaption of the mixer
runtime
-
-
time
adjustment time
00:00 ... 23:45
23:30
Chimney sweeper
Chimney sweeper function
Yes, no
no
Frost protection
antifreeze option
Yes, no
Yes
sensor
antifreeze option sensor
Flow, outdoor
Flow
antifr. temp.
antifreeze temperature
-20 ... +10 °C
+4 °C
Flow set
set flow temperature
10 ... 50 °C
20 °C
runtime
antifreeze runtime
15 ... 240 min
30 min
DHW priority
DHW priority option
Yes, no
no
Funct.
activation / Deactivation
activ., Deactivated
Deactivated
Chimney sweeper function
the chimney sweeper function can be used for ena-
bling a quick access to measurement conditions
without menu operation for the chimney sweeper.
If the chimney sweeper function is activated, the
chimney sweeper mode can be accessed by press-
ing button
6
for 5 seconds.
In the chimney sweeper mode, the heating circuit
mixer closes, the loading pump and the afterheating
contact are activated. While the chimney sweeper
mode is active, the directional pad is illuminated.
additionally,
Chimney sweeper
and a countdown
of 30 minutes are indicated on the display.
When the countdown has elapsed, the chimney
sweeper mode is automatically deactivated. If, dur-
ing the countdown, button
6
is again pressed for
more than 10 seconds, the countdown starts again.
In order to abort the countdown and thus deac-
tivate the chimney sweeper mode, briefly press
button
6
.
Antifreeze option
the antifreeze option of the heating circuit can be
used to temporarily activate an inactive heating cir-
cuit during sudden temperature drops in order to
protect it from frost damage.
When the antifreeze option is activated, the tem-
perature at the allocated sensor is monitored. If
the temperatur falls below the adjusted
antifreeze
temperature,
the heating circuit is activated for the
adjusted runtime. antifreeze operation has its own
set flow temperature which can be changed in the
Flow set
channel.