
34
Adjustment channel
Description
Adjustment range / selection
Factory setting
Load. break
Loading break time
1 ... 5
2
Circ.
Circulation time
1 ... 60
15
Break speed
Pause speed
Yes, No
No
Speed
Pause speed
30 ... 100 %
30 %
Pump delay
Pump delay
Yes, No
No
Delay
Delay time
5 ... 600
15
ding process stops and the controller monitors the
increase in collector temperature during the loading
break time
Load. break.
If it increases by 2 K [4° ra],
the break time timer starts again to allow the collec-
tor to gain more heat. If the collector temperature
does not increase sufficiently, the subordinate store
will be loaded again for the
Circ.
time as before.
as soon as the switch-on condition of the priority
store is fulfilled, it will be loaded. If the switch-on
condition of the priority store is not fulfilled, loading
of the second store will be continued. If the priority
store reaches its maximum temperature, sequence
controlled loading will not be carried out.
If store sequence control is active and the system
switches to load the priority store, the parameter
Load. break
also acts as a stabilisation timer, during
which the switch-off condition is ignored while the
system operation stabilises.
Loading logic
Solar / Basic settings / Loading logic
8.2
Solar optional functions
In this menu, additional functions can be selected
and adjusted for the solar part of the arrangement.
By selecting
Add new function...
, different pre-
programmed functions can be selected. the optio-
nal functions are available as long as free relays are
available.
When a function is selected, a submenu opens in
which all adjustments required can be made.
With this menu item, a relay and, if necessary, certain
system components can be allocated to the func-
tion.
In systems with 2 or more stores, loading logic ad-
justments can be made in this menu.
In systems 1 and 2, only the menu item
Pump delay
will be available.
If the priority store cannot be loaded, the subordina-
te store next in priority is checked. If useful heat can
be added, it will be loaded for the circulation time
(
Circ.
– factory setting 15 min.) after this, the loa-
295931-36390-8667 SOM 8 plus_en.indb 34
20.10.2011 13:14:36