62
Heating / HCs / New HC / Internal
adjustment channel Description
adjustment range / selection Factory setting
HC pump
Heating circuit pump
system dependent
system dependent
mixer open
relay selection mixer open
system dependent
system dependent
mixer closed
relay selection mixer closed
system dependent
system dependent
Flow sensor
Flow sensor selection
system dependent
system dependent
sen. outd.
outdoor sensor selection
system dependent
system dependent
Heating curve
Heating curve
0.3 ... 3.0
1.0
Day correction
Day correction
-5 ... +45 K
0 K
tflowmax
maximum flow temperature
10 ... 100 °C
50 °C
mode
operation mode
summer off, ext. switch, both
summer off
tsummer
summer temperature day
0 ... 40 °C
20 °C
Daytime on
Daytime on
00:00 ... 23:45
00:00
Daytime off
Daytime off
00:00 ... 23:45
00:00
tnight
summer temperature night
0 ... 40 °C
14 °C
ext. switch
external switch sensor input selec-
tion
system dependent
system dependent
remote control
remote control option
Yes, no
no
sen. rem.control
remote control sensor input selection system dependent
system dependent
timer
timer option
Yes, no
no
mode
timer mode
Day / night, Day / off
Day / night
night corr.
night correction
-20 ... +30 K
-5 K
timer
timer
-
-
Days of the week
Day selection
all days, monday ... sunday,
Continue
-
timer
time frame adjustment
00:00 ... 23:45
-
room therm. 1 ... 5
room thermostat option (1 ... 5)
Yes, no
no
type
room thermostat type selection
sensor, switch
sensor
sen. rtH
rtH sensor input selection
system dependent
system dependent
troom
room temperature
10 ... 30 °C
18 °C
timer
rtH timer
Yes, no, Inactive
no
295931-36390-8667 SOM 8 plus_en.indb 62