Issue 1
5
6 DEEP SEA 7310 Operating instructions
6.1 Controls
Control of the module is via push buttons mounted on the front of the module with
Stop/Reset Mode
,
Manual Mode
,
Auto Mode
and
Start
functions. For normal operation, these are the only controls
which need to be operated. Details of their operation are provided later in this document.
DSE 7310
Control push buttons
Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions
for which the triggering criteria have been removed. If the engine is running and the module
is in Stop mode, the module will automatically instruct the changeover device to unload the
generator. The fuel supply de-energises and the engine comes to a standstill. Should a
remote start signal
be present while operating in this mode, a remote start will not occur.
Manual
This mode allows manual control of the generator functions. Once in Manual mode the
module will respond to the start
button, start the engine, and run off load. If the engine is
running off-load in the Manual mode and a remote start signal becomes present, the module
will automatically instruct the changeover device to place the generator on load (‘Close
Generator’ beco
mes active (if used)). Upon removal of the remote start signal, the generator
remains on load until either selection of the ‘STOP/RESET’ or ‘AUTO’ modes.
For further details, please see the more detailed description of ‘Manual operation’ elsewhere
in this manual.