Stephill SSDP120 Handbook Download Page 16

 

 

Issue 1                                                                                                                       

14 

Display 

Reason 

ECU DATA FAIL 

The module is configured for CAN operation and does not detect data on 
the engine Can datalink, the engine shuts down. 

ECU SHUTDOWN 

The engine ECU has detected a shutdown alarm and has informed the 
DSE module of this situation. The exact error is also indicated on the 

module’s display.

 

kW OVERLOAD 

The measured Total kW is above the setting of the kW overload 
shutdown alarm 

NEGATIVE PHASE SEQUENCE 
 

Indicates ‘out of balance’ current loading of the generator.

 

Sometimes also called Negative Sequence Current or Symmetry Fault 

MAINTENANCE DUE 
 

Indicates that the maintenance alarm has triggered. A visit is required by 
the Generator service company. 500Hrs 

GENERATOR HIGH CURRENT 

A High Current condition has continued for an excess period, then the 
alarm escalates to either a shutdown or electrical trip condition 
(depending upon module configuration). For further details of the high 
current alarm, please see High Current Shutdown / Electrical Trip Alarm. 

LOADING VOLTAGE NOT 
REACHED 

Indicates that the generator voltage is not above the configured 

loading 

voltage 

after the safety timer. The generator will shutdown. 

LOADING FREQUENCY NOT 
REACHED 

Indicates that the generator frequency is not above the configured 

loading frequency 

after the safety timer

The generator will shutdown. 

PROTECTIONS DISABLED 

Shutdown and electrical trip alarms can be disabled by user 
configuration. In this case, Protections Disabled will appear on the 
module display; The alarm text will be displayed but the engine will 

continue to run. This is ‘logged’ by 

the module to allow DSE Technical 

Staff to check if the protections have been disabled on the module at any 
time.  

POSITIVE VAr 

Positive VArs has exceeded the trip settings. 

NEGATIVE VAr 

Negative VArs has exceeded the trip settings. 

  
7.2.3 IDMT ALARM 

If the 

IDMT Alarm 

is enabled, the controller begins following the IDMT ‘curve’ when the 

trip 

level is passed. 

If the 

Trip 

is surpassed for an excess amount of time the 

IDMT Alarm 

triggers (

Shutdown 

or 

Electric trip 

as selected 

in 

Action

). 

 

High current shutdown 

is a latching alarm and stops the Generator. 

Remove the fault then press the 

Stop/Reset Mode 

 

button to reset the module. 

 

High current electrical trip 

is a latching alarm and stops the Generator. 

Remove the fault then press the 

Stop/Reset Mode 

button to reset the module. 

 
The higher the overload, the faster the trip. The speed of the trip is dependent upon the fixed formula: 

 

T = t / ((IA / IT) 

 1) 2 

Where: T is the tripping time in seconds 

IA is the actual current of the most highly loaded line (L1 or L2 or L3) 
IT is the delayed over-current trip point 
t is the time multiplier setting and also represents the tripping time in seconds at twice full load (when IA / IT 
= 2). 

Factory settings for the 

IDMT Alarm 

when used on a brushless alternator are as follows (screen capture from the 

DSE Configuration Suite PC software : 
 

 

 

IT (Trip setting value) 

t (time multiplier)

 

Summary of Contents for SSDP120

Page 1: ...generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS STEPHILL GE...

Page 2: ...s 5 6 6 2 Manual mode 6 6 2 1 Waiting in manual mode 6 6 2 2 Starting sequence 6 6 2 3 Stopping sequence 7 6 3 Automatic mode 7 6 3 1 Waiting in auto mode 7 6 3 2 Starting sequence 7 6 3 3 Stopping se...

Page 3: ...ng of the acoustic lining It is important to keep the generator clean and well serviced in particular keep all air vents louvers clear of debris to prevent poor performance or possible overheating and...

Page 4: ...osed of accordingly Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local National regulations dependant on site location etc 4 4...

Page 5: ...equipped with an oil pressure and temperature switch and will shut down for low oil pressure and high engine temperature x Inspect the generator visually for signs of fault or damage x Ensure battery...

Page 6: ...K 1 With c d in position 1 K 10 4 Push button for Test 5 Push button for manual reset 6 Signalling green LED for Aux Supply presence 7 Signalling red LED for relay tripped 8 Terminals for Aux Supply...

Page 7: ...angeover device to unload the generator The fuel supply de energises and the engine comes to a standstill Should a remote start signal be present while operating in this mode a remote start will not o...

Page 8: ...u navigation Used for navigating the instrumentation event log and configuration screens For further details please see the more detailed description of these items elsewhere in this manual 6 2 MANUAL...

Page 9: ...ich the next start attempt is made Should this sequence continue beyond the Set Number Of Attempts the start sequence is terminated and the display shows Fail to Start The starter motor is disengaged...

Page 10: ...on Suite Software Alternatively to scroll manually through all instruments on the currently selected page press the scroll buttons The autoscroll is disabled To re enable autoscroll press the scroll b...

Page 11: ...VAh kVArh Generator Phase Sequence Dual Mutual Status 6 5 4 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7310 controller displays alarm status messages from the ECU Press to access t...

Page 12: ...he instruments press the next page button to select the next instrumentation page 6 6 ECU OVERRIDE When the ECU is powered down when in STOP mode it is not possible to read the diagnostic trouble code...

Page 13: ...Generator Voltage ph N Generator Voltage ph ph Generator Frequency Generator Current A Generator Load ph N kW Generator Total Load kW Generator Load ph N kVA Generator Total Load kVA Generator Power F...

Page 14: ...CU WARNING The engine ECU has detected a warning alarm and has informed the DSE module of this situation The exact error is also indicated on the module s display and action taken depending upon the s...

Page 15: ...fter the pre set number of start attempts EMERGENCY STOP The emergency stop button has been depressed This a failsafe normally closed to battery positive input and will immediately stop the set should...

Page 16: ...rical trip alarms can be disabled by user configuration In this case Protections Disabled will appear on the module display The alarm text will be displayed but the engine will continue to run This is...

Page 17: ...Suite Maintenance section x Pressing and holding the stop button when the module s display is on the maintenance alarm section ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is...

Page 18: ...te Start Check that the oil pressure switch or sensor is indicating low oil pressure to the controller Depending upon configuration then set will not start if oil pressure is not low Pre heat inoperat...

Page 19: ...for loose wires on the DC connector plug socket charge alternator Check continuity of all wires from charge alternator Refer to wiring diagram Check voltage at battery while generator is running volta...

Page 20: ...250S FRAME 200A 3POLE MCCB 036 0108 125A 3 POLE MCB 036 0109 63A 3 POLE MCB 036 0110 32A 3 POLE MCB 036 0111 32A 1 POLE MCB 036 0112 16A 1 POLE MCB 038 0114 HARD WIRE TERMINAL TWIN POST 038 0115 HARD...

Page 21: ...14 5 023 1019 CAM 28mm RAD LOCK 1000 28 023 1020 INSERT SLOT 2X4 RAD LOCK 1000 U142 023 1021 HOUSING RAD LOCK 1000 U223 023 1027 DOOR HINGE M8 023 1029 HINGE RADIATOR FLAP 1110 U24 024 1001 HANDLE SLA...

Page 22: ...into the cylinder is low and consequently the cylinder pressure is lower and so is the temperature The result is the piston is not such a good fit in the bore with increased clearance allowing more oi...

Page 23: ...spare parts required should be of genuine manufacturer s origin http www meccalte com 12 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despat...

Page 24: ...4 00 4291 00 00 4 00 00 4291 00 7 00 4 1 29 4 9 4 6 40 1 5 00 4 00 7 00 7 00 00 4 00 4291 00 00 4 00 4 00 00 4291 00 7 00 7 00 4 00 00 00 00 3 6421 5 00 4291 00 00 7 00 4291 00 00 00 00 4291 00 7 00...

Page 25: ...22 11 1 22 8 931 77 78 8 1 392 67 62 3 1 392 67 1 1 43 6 3 41 3 6 3 92 6 7 6 58 43 60 37 6 7 5 78 92 6 7 7 43 8 779 3 6 3 5 1 8643 7 88 6 22 22 22 88 6 22 22 22 22 22 22 22 22 22 19 8 22 22 22 22 19 8...

Page 26: ...Control panel door 1 24 16 512 SSDP120 Hard wire door 1 25 16 527 SSDP120 Radiator door 1 26 16 511 SSDP120 Bund blank plate 1 27 16 506 SSDP120 Perkins 1104 radiator plate 1 28 16 530 SSD110 Air outl...

Page 27: ...8 27 26 25 30 3 40 33 37 38 39 9 18 15 R Golding A 13 10 15 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP120 Canopy exploded view 16 548 STEPHI...

Reviews: