5.6 Variable RCD ELR-3C 

The  RCD  and  Bypass  switch  should  only  be  adjusted  or  switched  by  an  electrician  with  the 
appropriate test equipment. 
ELR-3C Earth Leakage Relay Description 
Its  wide  setting  ranges  allows  user  to  select  the  tripping  current,  in  order  that  the  contact  voltage 
values are maintained below 50V as required by the CEI 64-8Standard. 
This is also the suitable answer for a proper selectivity, whenever 

there are other ELR’s or/and RCD’s 

downstream or upstream in the line to be protected. 
An  outstanding  characteristic  of  the  present  relays,  is  the  permanent  control  of  the  Toroidal  -  ELR 
circuit. 
Its interruption brings along the immediate trip of the protection. This allows to identify the anomaly, 
without waiting to the periodical control, made with the Test push button. 
The instrument, fitted with filters at the input circuits, is practically immune to external disturbances, 
so  as  the  pulse  currents  with  dc  components,  complying  with  the  requirements  of  VDE  0664  and 
project IEC 23 Standards. 
The ELR-3C has the possibility of an automatic or manual reset, selectable by a micro switch and to 
protect the settings by its sealable transparent front cover. 

 

1) Current tripping setting potentiometer. 
2) Tripping time setting potentiometer. 
3) Micro switches for programming: 
-a In position 1 automatic reset, In position 0 
manual reset. 
-b Selection of the multiplying constant. 
Tripping time, in position 1 K=10 in position 0 
K=1  
c,d Selection of the multiplying constant of 
tripping current: 
With c d in position 0 K=0.1 
With c in position 1, d in position 0 K=1  
With c,d in position 1 K=10 
4) Push button for Test. 
5) Push button for manual reset. 
6) Signalling green LED for Aux. Supply 
presence. 
7) Signalling red LED for relay tripped. 
8) Terminals for Aux. Supply. 

  9) Output terminals for end relays 
10) Connection terminals to T/T CT-1 
 

 
5.7 Hard wire terminals 

Do not attempt to work on the hard wire terminals while the set is running, hard wire door is fitted with a 
magnetic switch to shut down generator if door is opened. 
The generator is fitted with hard wire terminals which are located under the Circuit breakers, the terminals are 
clearly marked for 400Volt. They can be accessed by either drilling the steel gland plate or passing the cables 
through the rubber gland plate. If cables are passed through the rubber gland plate they must be secured with 
the cable clamp to prevent strain on terminals. The gland plate should be re-fitted prior to running generator. 

 
5.8 Remote start terminals 

The generator is equipped with a pair of normally open contacts which will start the generator when closed. 

 
5.9 Long term storage 

For storage or long periods of inactivity, Stephill Generators recommend the following: 
Generators should be stored with oil filled to the correct capacity; Storage periods of 18 months and over may 
require special lubricants and treatments. If so please seek further advice from the engine manufacturer. 
Before the generator is used after long term storage, all fuels and oils should be replaced. 
Generator mounts, pipes and hoses should be checked to ensure that they are un-perished following 
extended periods of storage. 
The generator should be stored in a clean dry area, ideally having a reasonable constant ambient 
temperature, and ideally not below freezing. The battery isolator switch should be switched off. 

 
 

Summary of Contents for SSDP120

Page 1: ...generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS STEPHILL GE...

Page 2: ...s 5 6 6 2 Manual mode 6 6 2 1 Waiting in manual mode 6 6 2 2 Starting sequence 6 6 2 3 Stopping sequence 7 6 3 Automatic mode 7 6 3 1 Waiting in auto mode 7 6 3 2 Starting sequence 7 6 3 3 Stopping se...

Page 3: ...ng of the acoustic lining It is important to keep the generator clean and well serviced in particular keep all air vents louvers clear of debris to prevent poor performance or possible overheating and...

Page 4: ...osed of accordingly Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local National regulations dependant on site location etc 4 4...

Page 5: ...equipped with an oil pressure and temperature switch and will shut down for low oil pressure and high engine temperature x Inspect the generator visually for signs of fault or damage x Ensure battery...

Page 6: ...K 1 With c d in position 1 K 10 4 Push button for Test 5 Push button for manual reset 6 Signalling green LED for Aux Supply presence 7 Signalling red LED for relay tripped 8 Terminals for Aux Supply...

Page 7: ...angeover device to unload the generator The fuel supply de energises and the engine comes to a standstill Should a remote start signal be present while operating in this mode a remote start will not o...

Page 8: ...u navigation Used for navigating the instrumentation event log and configuration screens For further details please see the more detailed description of these items elsewhere in this manual 6 2 MANUAL...

Page 9: ...ich the next start attempt is made Should this sequence continue beyond the Set Number Of Attempts the start sequence is terminated and the display shows Fail to Start The starter motor is disengaged...

Page 10: ...on Suite Software Alternatively to scroll manually through all instruments on the currently selected page press the scroll buttons The autoscroll is disabled To re enable autoscroll press the scroll b...

Page 11: ...VAh kVArh Generator Phase Sequence Dual Mutual Status 6 5 4 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7310 controller displays alarm status messages from the ECU Press to access t...

Page 12: ...he instruments press the next page button to select the next instrumentation page 6 6 ECU OVERRIDE When the ECU is powered down when in STOP mode it is not possible to read the diagnostic trouble code...

Page 13: ...Generator Voltage ph N Generator Voltage ph ph Generator Frequency Generator Current A Generator Load ph N kW Generator Total Load kW Generator Load ph N kVA Generator Total Load kVA Generator Power F...

Page 14: ...CU WARNING The engine ECU has detected a warning alarm and has informed the DSE module of this situation The exact error is also indicated on the module s display and action taken depending upon the s...

Page 15: ...fter the pre set number of start attempts EMERGENCY STOP The emergency stop button has been depressed This a failsafe normally closed to battery positive input and will immediately stop the set should...

Page 16: ...rical trip alarms can be disabled by user configuration In this case Protections Disabled will appear on the module display The alarm text will be displayed but the engine will continue to run This is...

Page 17: ...Suite Maintenance section x Pressing and holding the stop button when the module s display is on the maintenance alarm section ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is...

Page 18: ...te Start Check that the oil pressure switch or sensor is indicating low oil pressure to the controller Depending upon configuration then set will not start if oil pressure is not low Pre heat inoperat...

Page 19: ...for loose wires on the DC connector plug socket charge alternator Check continuity of all wires from charge alternator Refer to wiring diagram Check voltage at battery while generator is running volta...

Page 20: ...250S FRAME 200A 3POLE MCCB 036 0108 125A 3 POLE MCB 036 0109 63A 3 POLE MCB 036 0110 32A 3 POLE MCB 036 0111 32A 1 POLE MCB 036 0112 16A 1 POLE MCB 038 0114 HARD WIRE TERMINAL TWIN POST 038 0115 HARD...

Page 21: ...14 5 023 1019 CAM 28mm RAD LOCK 1000 28 023 1020 INSERT SLOT 2X4 RAD LOCK 1000 U142 023 1021 HOUSING RAD LOCK 1000 U223 023 1027 DOOR HINGE M8 023 1029 HINGE RADIATOR FLAP 1110 U24 024 1001 HANDLE SLA...

Page 22: ...into the cylinder is low and consequently the cylinder pressure is lower and so is the temperature The result is the piston is not such a good fit in the bore with increased clearance allowing more oi...

Page 23: ...spare parts required should be of genuine manufacturer s origin http www meccalte com 12 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despat...

Page 24: ...4 00 4291 00 00 4 00 00 4291 00 7 00 4 1 29 4 9 4 6 40 1 5 00 4 00 7 00 7 00 00 4 00 4291 00 00 4 00 4 00 00 4291 00 7 00 7 00 4 00 00 00 00 3 6421 5 00 4291 00 00 7 00 4291 00 00 00 00 4291 00 7 00...

Page 25: ...22 11 1 22 8 931 77 78 8 1 392 67 62 3 1 392 67 1 1 43 6 3 41 3 6 3 92 6 7 6 58 43 60 37 6 7 5 78 92 6 7 7 43 8 779 3 6 3 5 1 8643 7 88 6 22 22 22 88 6 22 22 22 22 22 22 22 22 22 19 8 22 22 22 22 19 8...

Page 26: ...Control panel door 1 24 16 512 SSDP120 Hard wire door 1 25 16 527 SSDP120 Radiator door 1 26 16 511 SSDP120 Bund blank plate 1 27 16 506 SSDP120 Perkins 1104 radiator plate 1 28 16 530 SSD110 Air outl...

Page 27: ...8 27 26 25 30 3 40 33 37 38 39 9 18 15 R Golding A 13 10 15 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP120 Canopy exploded view 16 548 STEPHI...

Reviews: