Stephill SSDP120 Handbook Download Page 19

 

 

Issue 1                                                                                                                       

17 

9 Fault finding general 
Fault 

Action 

High engine  

Check Water/Antifreeze level in the radiator. 

temperature 

Check for loose wires on the temperature switch & DC loom connector block. 

 

Check the continuity of the earth wire. (Refer to wiring diagram) 

 

Check radiator surface (both sides) and fins are not obstructed. 

 

Check operation of the Temperature switch. 

 

Check that the generator air inlets and outlets are not obstructed. 

 

Check the fan belt is not damaged, broken or loose. (Refer to handbook) 

 

Note you may experience low charge if fan belt is loose. 

Low oil pressure 

Check Oil level and fill to correct level if necessary 

 

Check operation of Oil switch. 

HZ & Voltage  

Check reset button not tripped and reset if required. 

shutdown 

Check AC Input at module.  

 

Check engine speed is set to 50Hz at no load. 

 

Check AC supply from alternator. (If no output refer to alternator handbook) 

 

Check fuse on AVR. 

 

Check engine has been regularly serviced. 

No power to  

Check fuse. 

control 

Check 12V DC supply to module. If supply present but not operational try new unit. 

module 

Check battery voltage. 

 

Check battery isolator switch is on. 

 

Check for loose wires on battery isolator. 

 

Check for loose wires on the DC connector plug and socket. 

 

Check continuity on +VE and -VE wires to battery. 

Battery not  

Note you may experience low charge if fan belt is loose. 

charging 

Check for loose wires on the DC connector plug / socket & charge alternator. 

 

Check continuity of all wires from charge alternator. (Refer to wiring diagram) 

 

Check voltage at battery while generator is running, voltage should be 13.4 - 14.4V. 

 

Check battery voltage is above 12.5V. 

Engine not  

Check Oil level and fill to correct level if necessary. 

starting 

Check fuel level. 

 

Check 3 way valves are in correct position. (If fitted) 

 

Check operation of fuel lift pump. 

Glow plugs not 

Check Emergency stop. 

operating 

Check the fuses. 

 

Check battery voltage is above 12.5V.  
Check for loose wires on the Glow plug, relays, fuses, module terminals, plug and socket. 
Check -VE supply. 

 

Check +VE on Glow plug & trace back to battery via relay. 

 

Check +VE on Glow plug & trace back to module via relay, plug & socket. 

Starter Motor not   Check Emergency stop. 
operating 

Check the fuses. 

 

Check battery voltage is above 12.5V. 

Starter Motor not 

Check for loose wires on the solenoid, relays, fuses, module terminals, plug and socket. 

operating 

Check +VE supply from battery to starter motor via isolator switch. 

 

Check -VE supply. 

 

Check start terminal on Starter motor & trace back to module via relay, plug & socket. 

Fuel solenoid not   Does the Fuel solenoid energises when the starter motor turns over. 
operating 

Check Emergency stop. 

 

Check the fuses. 

 

Check battery voltage is above 12.5V. 

 

Check for loose wires on the solenoid, relays, fuses, module terminals, plug and socket. 

 

Check -VE supply. 

 

Check +VE on Fuel solenoid & trace back to battery via relay. 

 

Check +VE on Fuel solenoid & trace back to module via relay, plug & socket. 

Summary of Contents for SSDP120

Page 1: ...generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS STEPHILL GE...

Page 2: ...s 5 6 6 2 Manual mode 6 6 2 1 Waiting in manual mode 6 6 2 2 Starting sequence 6 6 2 3 Stopping sequence 7 6 3 Automatic mode 7 6 3 1 Waiting in auto mode 7 6 3 2 Starting sequence 7 6 3 3 Stopping se...

Page 3: ...ng of the acoustic lining It is important to keep the generator clean and well serviced in particular keep all air vents louvers clear of debris to prevent poor performance or possible overheating and...

Page 4: ...osed of accordingly Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local National regulations dependant on site location etc 4 4...

Page 5: ...equipped with an oil pressure and temperature switch and will shut down for low oil pressure and high engine temperature x Inspect the generator visually for signs of fault or damage x Ensure battery...

Page 6: ...K 1 With c d in position 1 K 10 4 Push button for Test 5 Push button for manual reset 6 Signalling green LED for Aux Supply presence 7 Signalling red LED for relay tripped 8 Terminals for Aux Supply...

Page 7: ...angeover device to unload the generator The fuel supply de energises and the engine comes to a standstill Should a remote start signal be present while operating in this mode a remote start will not o...

Page 8: ...u navigation Used for navigating the instrumentation event log and configuration screens For further details please see the more detailed description of these items elsewhere in this manual 6 2 MANUAL...

Page 9: ...ich the next start attempt is made Should this sequence continue beyond the Set Number Of Attempts the start sequence is terminated and the display shows Fail to Start The starter motor is disengaged...

Page 10: ...on Suite Software Alternatively to scroll manually through all instruments on the currently selected page press the scroll buttons The autoscroll is disabled To re enable autoscroll press the scroll b...

Page 11: ...VAh kVArh Generator Phase Sequence Dual Mutual Status 6 5 4 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7310 controller displays alarm status messages from the ECU Press to access t...

Page 12: ...he instruments press the next page button to select the next instrumentation page 6 6 ECU OVERRIDE When the ECU is powered down when in STOP mode it is not possible to read the diagnostic trouble code...

Page 13: ...Generator Voltage ph N Generator Voltage ph ph Generator Frequency Generator Current A Generator Load ph N kW Generator Total Load kW Generator Load ph N kVA Generator Total Load kVA Generator Power F...

Page 14: ...CU WARNING The engine ECU has detected a warning alarm and has informed the DSE module of this situation The exact error is also indicated on the module s display and action taken depending upon the s...

Page 15: ...fter the pre set number of start attempts EMERGENCY STOP The emergency stop button has been depressed This a failsafe normally closed to battery positive input and will immediately stop the set should...

Page 16: ...rical trip alarms can be disabled by user configuration In this case Protections Disabled will appear on the module display The alarm text will be displayed but the engine will continue to run This is...

Page 17: ...Suite Maintenance section x Pressing and holding the stop button when the module s display is on the maintenance alarm section ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is...

Page 18: ...te Start Check that the oil pressure switch or sensor is indicating low oil pressure to the controller Depending upon configuration then set will not start if oil pressure is not low Pre heat inoperat...

Page 19: ...for loose wires on the DC connector plug socket charge alternator Check continuity of all wires from charge alternator Refer to wiring diagram Check voltage at battery while generator is running volta...

Page 20: ...250S FRAME 200A 3POLE MCCB 036 0108 125A 3 POLE MCB 036 0109 63A 3 POLE MCB 036 0110 32A 3 POLE MCB 036 0111 32A 1 POLE MCB 036 0112 16A 1 POLE MCB 038 0114 HARD WIRE TERMINAL TWIN POST 038 0115 HARD...

Page 21: ...14 5 023 1019 CAM 28mm RAD LOCK 1000 28 023 1020 INSERT SLOT 2X4 RAD LOCK 1000 U142 023 1021 HOUSING RAD LOCK 1000 U223 023 1027 DOOR HINGE M8 023 1029 HINGE RADIATOR FLAP 1110 U24 024 1001 HANDLE SLA...

Page 22: ...into the cylinder is low and consequently the cylinder pressure is lower and so is the temperature The result is the piston is not such a good fit in the bore with increased clearance allowing more oi...

Page 23: ...spare parts required should be of genuine manufacturer s origin http www meccalte com 12 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despat...

Page 24: ...4 00 4291 00 00 4 00 00 4291 00 7 00 4 1 29 4 9 4 6 40 1 5 00 4 00 7 00 7 00 00 4 00 4291 00 00 4 00 4 00 00 4291 00 7 00 7 00 4 00 00 00 00 3 6421 5 00 4291 00 00 7 00 4291 00 00 00 00 4291 00 7 00...

Page 25: ...22 11 1 22 8 931 77 78 8 1 392 67 62 3 1 392 67 1 1 43 6 3 41 3 6 3 92 6 7 6 58 43 60 37 6 7 5 78 92 6 7 7 43 8 779 3 6 3 5 1 8643 7 88 6 22 22 22 88 6 22 22 22 22 22 22 22 22 22 19 8 22 22 22 22 19 8...

Page 26: ...Control panel door 1 24 16 512 SSDP120 Hard wire door 1 25 16 527 SSDP120 Radiator door 1 26 16 511 SSDP120 Bund blank plate 1 27 16 506 SSDP120 Perkins 1104 radiator plate 1 28 16 530 SSD110 Air outl...

Page 27: ...8 27 26 25 30 3 40 33 37 38 39 9 18 15 R Golding A 13 10 15 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP120 Canopy exploded view 16 548 STEPHI...

Reviews: