Issue 1
16
Repeat this process for the other digits of the PIN number. You can press
(left) if you need to
move back to adjust one of the previous digits.
When
is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not
correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed:
8 Fault finding 7310
Symptom
Possible Remedy
Unit is inoperative
Read/Write configuration
does not operate
Check the battery and wiring to the unit. Check the DC supply.
Check the DC fuse.
Unit shuts down
Check DC supply voltage is not above 35 Volts or below 9 Volts
Check the operating temperature is not above 70°C. Check the DC fuse.
Unit locks out on
Emergency Stop
Check emergency stop switch is functioning correctly.
Check Wiring is not open circuit.
Warning fault operates
Check relevant switch and wiring of fault indicated on LCD display. Check
configuration of input.
Fail to Start is activated
after pre-set number of
attempts to start
Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery
supply is present on the Fuel output of the module. Check the speed sensing
signal is present on the 7000 series module’s inputs. Refer to engine manual.
LE
Continuous starting of
generator when in
AUTO
Check that there is no signal present on the “Remote Start” input.
Generator fails to start on
receipt of Remote Start
signal.
Check Start Delay timer has timed out.
Check signal is on “Remote Start” input. Confirm correct configuration of input
is configured to be used as “Remote Start”.
Check that the oil pressure switch or sensor is indicating low oil pressure to
the controller. Depending upon configuration, then set will not start if oil
pressure is not low.
Pre-heat inoperative
Check wiring to engine heater plugs. Check battery supply. Check battery
supply is present on the Pre-heat output of module.
Starter motor inoperative
Check wiring to starter solenoid. Check battery supply. Check battery supply
is present on the Starter output of module. Ensure that the Emergency Stop
input is at Positive. Ensure oil pressure switch or sensor is indicating the
“low
oil pressure” state to the 731
0 series controller.
Engine runs but
generator will not
take load
Check Warm up timer has timed out. Ensure generator load inhibit signal is
not present on the module inputs. Check connections to the switching device.
Note that the set will not take load in manual mode unless there is an active
remote start on load signal.
Incorrect reading on
Engine gauges
Check engine is operating correctly. Check sensor and wiring paying
particular attention to the wiring to terminal 15.
Set will not take load
Ensure the generator available LED is lit
Check that the output configuration is correct to drive the load switch device
and that all connections are correct.
Remember that the set will not take load in manual mode unless a remote
start on load input is present or the close generator button is pressed.
NOTE: The PIN number is not set by DSE when the module leaves the factory. The module has a
PIN code set, this has been set by Stephill If the code has been changed then
‘lost’ or ‘forgotten’, the
module must be returned to the DSE factory to have
the module’s code removed. A charge will be
made for this procedure. NB - This procedure cannot be performed away from the DSE factory.