Repeat this process for the other digits of the PIN number. You can press 

 (left) if you need to 

move back to adjust one of the previous digits. 
When 

 is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is not 

correct, you must re-enter the PIN.
If the PIN has been successfully entered (or the module PIN has not been enabled), the editor is displayed: 

 

 
8 Fault finding 7310 
Symptom 

Possible Remedy 

Unit is inoperative 
Read/Write configuration 
does not operate

 

Check the battery and wiring to the unit. Check the DC supply.  
Check the DC fuse.

 

Unit shuts down 

Check DC supply voltage is not above 35 Volts or below 9 Volts 
Check the operating temperature is not above 70°C. Check the DC fuse. 

Unit locks out on 
Emergency Stop 

Check emergency stop switch is functioning correctly.  
Check Wiring is not open circuit. 

Warning fault operates 

Check relevant switch and wiring of fault indicated on LCD display. Check 
configuration of input. 

Fail to Start is activated 
after pre-set number of 
attempts to start 

Check wiring of fuel solenoid. Check fuel. Check battery supply. Check battery 
supply is present on the Fuel output of the module. Check the speed sensing 

signal is present on the 7000 series module’s inputs. Refer to engine manual.

LE

 

Continuous starting of 
generator when in 

AUTO

 

Check that there is no signal present on the “Remote Start” input. 

 

 

Generator fails to start on 
receipt of Remote Start 
signal. 
 

Check Start Delay timer has timed out. 

Check signal is on “Remote Start” input. Confirm correct configuration of input

 

is configured to be used as “Remote Start”.

 

Check that the oil pressure switch or sensor is indicating low oil pressure to 
the controller. Depending upon configuration, then set will not start if oil 
pressure is not low. 

Pre-heat inoperative  

 

Check wiring to engine heater plugs. Check battery supply. Check battery 
supply is present on the Pre-heat output of module. 

 

Starter motor inoperative  

 

Check wiring to starter solenoid. Check battery supply. Check battery supply 
is present on the Starter output of module. Ensure that the Emergency Stop 
input is at Positive. Ensure oil pressure switch or sensor is indicating the 

“low

 

oil pressure” state to the 731

0 series controller.

 

Engine runs but 
generator will not 
take load 

 

Check Warm up timer has timed out. Ensure generator load inhibit signal is 
not present on the module inputs. Check connections to the switching device. 
Note that the set will not take load in manual mode unless there is an active 
remote start on load signal.

 

Incorrect reading on 
Engine gauges

 

Check engine is operating correctly. Check sensor and wiring paying 
particular attention to the wiring to terminal 15.

 

Set will not take load

 

Ensure the generator available LED is lit 
Check that the output configuration is correct to drive the load switch device 
and that all connections are correct. 
Remember that the set will not take load in manual mode unless a remote 
start on load input is present or the close generator button is pressed.

 

 
 

NOTE: The PIN number is not set by DSE when the module leaves the factory. The module has a 

PIN code set, this has been set by Stephill If the code has been changed then 

‘lost’ or ‘forgotten’, the 

module must be returned to the DSE factory to have 

the module’s code removed. A charge will be 

made for this procedure. NB - This procedure cannot be performed away from the DSE factory.

 

Summary of Contents for SSDP120

Page 1: ...generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS STEPHILL GE...

Page 2: ...s 5 6 6 2 Manual mode 6 6 2 1 Waiting in manual mode 6 6 2 2 Starting sequence 6 6 2 3 Stopping sequence 7 6 3 Automatic mode 7 6 3 1 Waiting in auto mode 7 6 3 2 Starting sequence 7 6 3 3 Stopping se...

Page 3: ...ng of the acoustic lining It is important to keep the generator clean and well serviced in particular keep all air vents louvers clear of debris to prevent poor performance or possible overheating and...

Page 4: ...osed of accordingly Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local National regulations dependant on site location etc 4 4...

Page 5: ...equipped with an oil pressure and temperature switch and will shut down for low oil pressure and high engine temperature x Inspect the generator visually for signs of fault or damage x Ensure battery...

Page 6: ...K 1 With c d in position 1 K 10 4 Push button for Test 5 Push button for manual reset 6 Signalling green LED for Aux Supply presence 7 Signalling red LED for relay tripped 8 Terminals for Aux Supply...

Page 7: ...angeover device to unload the generator The fuel supply de energises and the engine comes to a standstill Should a remote start signal be present while operating in this mode a remote start will not o...

Page 8: ...u navigation Used for navigating the instrumentation event log and configuration screens For further details please see the more detailed description of these items elsewhere in this manual 6 2 MANUAL...

Page 9: ...ich the next start attempt is made Should this sequence continue beyond the Set Number Of Attempts the start sequence is terminated and the display shows Fail to Start The starter motor is disengaged...

Page 10: ...on Suite Software Alternatively to scroll manually through all instruments on the currently selected page press the scroll buttons The autoscroll is disabled To re enable autoscroll press the scroll b...

Page 11: ...VAh kVArh Generator Phase Sequence Dual Mutual Status 6 5 4 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7310 controller displays alarm status messages from the ECU Press to access t...

Page 12: ...he instruments press the next page button to select the next instrumentation page 6 6 ECU OVERRIDE When the ECU is powered down when in STOP mode it is not possible to read the diagnostic trouble code...

Page 13: ...Generator Voltage ph N Generator Voltage ph ph Generator Frequency Generator Current A Generator Load ph N kW Generator Total Load kW Generator Load ph N kVA Generator Total Load kVA Generator Power F...

Page 14: ...CU WARNING The engine ECU has detected a warning alarm and has informed the DSE module of this situation The exact error is also indicated on the module s display and action taken depending upon the s...

Page 15: ...fter the pre set number of start attempts EMERGENCY STOP The emergency stop button has been depressed This a failsafe normally closed to battery positive input and will immediately stop the set should...

Page 16: ...rical trip alarms can be disabled by user configuration In this case Protections Disabled will appear on the module display The alarm text will be displayed but the engine will continue to run This is...

Page 17: ...Suite Maintenance section x Pressing and holding the stop button when the module s display is on the maintenance alarm section ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is...

Page 18: ...te Start Check that the oil pressure switch or sensor is indicating low oil pressure to the controller Depending upon configuration then set will not start if oil pressure is not low Pre heat inoperat...

Page 19: ...for loose wires on the DC connector plug socket charge alternator Check continuity of all wires from charge alternator Refer to wiring diagram Check voltage at battery while generator is running volta...

Page 20: ...250S FRAME 200A 3POLE MCCB 036 0108 125A 3 POLE MCB 036 0109 63A 3 POLE MCB 036 0110 32A 3 POLE MCB 036 0111 32A 1 POLE MCB 036 0112 16A 1 POLE MCB 038 0114 HARD WIRE TERMINAL TWIN POST 038 0115 HARD...

Page 21: ...14 5 023 1019 CAM 28mm RAD LOCK 1000 28 023 1020 INSERT SLOT 2X4 RAD LOCK 1000 U142 023 1021 HOUSING RAD LOCK 1000 U223 023 1027 DOOR HINGE M8 023 1029 HINGE RADIATOR FLAP 1110 U24 024 1001 HANDLE SLA...

Page 22: ...into the cylinder is low and consequently the cylinder pressure is lower and so is the temperature The result is the piston is not such a good fit in the bore with increased clearance allowing more oi...

Page 23: ...spare parts required should be of genuine manufacturer s origin http www meccalte com 12 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despat...

Page 24: ...4 00 4291 00 00 4 00 00 4291 00 7 00 4 1 29 4 9 4 6 40 1 5 00 4 00 7 00 7 00 00 4 00 4291 00 00 4 00 4 00 00 4291 00 7 00 7 00 4 00 00 00 00 3 6421 5 00 4291 00 00 7 00 4291 00 00 00 00 4291 00 7 00...

Page 25: ...22 11 1 22 8 931 77 78 8 1 392 67 62 3 1 392 67 1 1 43 6 3 41 3 6 3 92 6 7 6 58 43 60 37 6 7 5 78 92 6 7 7 43 8 779 3 6 3 5 1 8643 7 88 6 22 22 22 88 6 22 22 22 22 22 22 22 22 22 19 8 22 22 22 22 19 8...

Page 26: ...Control panel door 1 24 16 512 SSDP120 Hard wire door 1 25 16 527 SSDP120 Radiator door 1 26 16 511 SSDP120 Bund blank plate 1 27 16 506 SSDP120 Perkins 1104 radiator plate 1 28 16 530 SSD110 Air outl...

Page 27: ...8 27 26 25 30 3 40 33 37 38 39 9 18 15 R Golding A 13 10 15 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP120 Canopy exploded view 16 548 STEPHI...

Reviews: