Stephill SSDP120 Handbook Download Page 15

 

 

Issue 1                                                                                                                       

13 

By default, warning alarms are self-

resetting when the fault condition is removed. However enabling ‘all w

arnings 

are latched’ will cause warning alarms to latch until reset manually. This is enabled using the 7000 series

 

configuration suite in conjunction with a compatible PC. 
 

7.2.1 HIGH CURRENT WARNING ALARM 
GENERATOR HIGH CURRENT

, if the module detects a generator output current in excess of the pre-set trip a 

warning alarm initiates. The module shows Alarm Warning High Current. If this high current condition continues for 
an excess period, then the alarm escalates to a shutdown condition. For further details of the high current alarm, 
please see High Current Shutdown Alarm.

  

High Current Warning Alarm is self-resetting when the overcurrent condition is removed. 

 
7.2.2 SHUTDOWNS 

Shutdowns are latching alarms and stop the Generator. Clear the alarm and remove the fault then press Stop/Reset 

 to reset the module. 

Example 

 

 

NOTE:- The alarm condition must be rectified before a reset will take place. If the alarm 

condition remains, it will not be possible to reset the unit (The exception to this is the Low Oil 
Pressure alarm and 

similar ‘active from safety on’ alarms, as the oil pressure will be low with the 

engine at rest).

 

 

Display 

Reason 

FAIL TO START

 

The engine has not fired after the pre-set number of start attempts

 

EMERGENCY STOP

 

The emergency stop button has been depressed. This a failsafe 
(normally closed to battery positive) input and will immediately stop the 
set should the signal be removed. 
Removal of the battery positive supply from the emergency stop input will 
also remove DC supply from the Fuel and Start outputs of the controller. 

 

NOTE:- The Emergency Stop Positive signal must be 

present otherwise the unit will shutdown.

 

FUEL USAGE 

Indicates the amount of fuel measured by the fuel level sensor is in 
excess of the 

Fuel Usage 

alarm settings. This often indicates a fuel leak 

or potential fuel theft.

 

PHASE ROTATION 

 

The phase rotation is measured as being different to the configured 
direction.

 

OVERSPEED

 

The engine speed has exceeded the pre-set trip

 

UNDERSPEED 

The engine speed has fallen below the pre-set trip after the 

Safety On 

timer has expired. 

GENERATOR OVER 
FREQUENCY 

The generator output frequency has risen above the preset level 
 

GENERATOR UNDER 
FREQUENCY 

The generator output frequency has fallen below the preset level 
 

GENERATOR OVER VOLTAGE 

The generator output voltage has risen above the preset level 
 

GENERATOR UNDER 
VOLTAGE 

The generator output voltage has fallen below the preset level 
 

OIL PRESSURE SENSOR 
OPEN CIRCUIT 

The oil pressure sensor is detected as not being present (open circuit) 

AUXILIARY INPUTS 

An active auxiliary input configured as a shutdown will cause the engine 
to shut down. The display shows text of the fault. 

 

 

Summary of Contents for SSDP120

Page 1: ...generators co uk Web Web www stephill generators co uk Northants NN8 6AG DO NOT OPERATE THE GENERATOR BEFORE READING THIS MANUAL AND ENGINE MANUFACTURER S OWNER S MANUAL AND WARNINGS THIS STEPHILL GE...

Page 2: ...s 5 6 6 2 Manual mode 6 6 2 1 Waiting in manual mode 6 6 2 2 Starting sequence 6 6 2 3 Stopping sequence 7 6 3 Automatic mode 7 6 3 1 Waiting in auto mode 7 6 3 2 Starting sequence 7 6 3 3 Stopping se...

Page 3: ...ng of the acoustic lining It is important to keep the generator clean and well serviced in particular keep all air vents louvers clear of debris to prevent poor performance or possible overheating and...

Page 4: ...osed of accordingly Warning Although this generator is fitted with a Bunded tank it is the duty of the owner to ensure that it meets with Local National regulations dependant on site location etc 4 4...

Page 5: ...equipped with an oil pressure and temperature switch and will shut down for low oil pressure and high engine temperature x Inspect the generator visually for signs of fault or damage x Ensure battery...

Page 6: ...K 1 With c d in position 1 K 10 4 Push button for Test 5 Push button for manual reset 6 Signalling green LED for Aux Supply presence 7 Signalling red LED for relay tripped 8 Terminals for Aux Supply...

Page 7: ...angeover device to unload the generator The fuel supply de energises and the engine comes to a standstill Should a remote start signal be present while operating in this mode a remote start will not o...

Page 8: ...u navigation Used for navigating the instrumentation event log and configuration screens For further details please see the more detailed description of these items elsewhere in this manual 6 2 MANUAL...

Page 9: ...ich the next start attempt is made Should this sequence continue beyond the Set Number Of Attempts the start sequence is terminated and the display shows Fail to Start The starter motor is disengaged...

Page 10: ...on Suite Software Alternatively to scroll manually through all instruments on the currently selected page press the scroll buttons The autoscroll is disabled To re enable autoscroll press the scroll b...

Page 11: ...VAh kVArh Generator Phase Sequence Dual Mutual Status 6 5 4 CAN ERROR MESSAGES When connected to a suitable CAN engine the 7310 controller displays alarm status messages from the ECU Press to access t...

Page 12: ...he instruments press the next page button to select the next instrumentation page 6 6 ECU OVERRIDE When the ECU is powered down when in STOP mode it is not possible to read the diagnostic trouble code...

Page 13: ...Generator Voltage ph N Generator Voltage ph ph Generator Frequency Generator Current A Generator Load ph N kW Generator Total Load kW Generator Load ph N kVA Generator Total Load kVA Generator Power F...

Page 14: ...CU WARNING The engine ECU has detected a warning alarm and has informed the DSE module of this situation The exact error is also indicated on the module s display and action taken depending upon the s...

Page 15: ...fter the pre set number of start attempts EMERGENCY STOP The emergency stop button has been depressed This a failsafe normally closed to battery positive input and will immediately stop the set should...

Page 16: ...rical trip alarms can be disabled by user configuration In this case Protections Disabled will appear on the module display The alarm text will be displayed but the engine will continue to run This is...

Page 17: ...Suite Maintenance section x Pressing and holding the stop button when the module s display is on the maintenance alarm section ACCESSING THE MAIN FRONT PANEL CONFIGURATION EDITOR Ensure the engine is...

Page 18: ...te Start Check that the oil pressure switch or sensor is indicating low oil pressure to the controller Depending upon configuration then set will not start if oil pressure is not low Pre heat inoperat...

Page 19: ...for loose wires on the DC connector plug socket charge alternator Check continuity of all wires from charge alternator Refer to wiring diagram Check voltage at battery while generator is running volta...

Page 20: ...250S FRAME 200A 3POLE MCCB 036 0108 125A 3 POLE MCB 036 0109 63A 3 POLE MCB 036 0110 32A 3 POLE MCB 036 0111 32A 1 POLE MCB 036 0112 16A 1 POLE MCB 038 0114 HARD WIRE TERMINAL TWIN POST 038 0115 HARD...

Page 21: ...14 5 023 1019 CAM 28mm RAD LOCK 1000 28 023 1020 INSERT SLOT 2X4 RAD LOCK 1000 U142 023 1021 HOUSING RAD LOCK 1000 U223 023 1027 DOOR HINGE M8 023 1029 HINGE RADIATOR FLAP 1110 U24 024 1001 HANDLE SLA...

Page 22: ...into the cylinder is low and consequently the cylinder pressure is lower and so is the temperature The result is the piston is not such a good fit in the bore with increased clearance allowing more oi...

Page 23: ...spare parts required should be of genuine manufacturer s origin http www meccalte com 12 WARRANTY All equipment supplied by STEPHILL GENERATORS LTD carries a warranty of 12 months from date of despat...

Page 24: ...4 00 4291 00 00 4 00 00 4291 00 7 00 4 1 29 4 9 4 6 40 1 5 00 4 00 7 00 7 00 00 4 00 4291 00 00 4 00 4 00 00 4291 00 7 00 7 00 4 00 00 00 00 3 6421 5 00 4291 00 00 7 00 4291 00 00 00 00 4291 00 7 00...

Page 25: ...22 11 1 22 8 931 77 78 8 1 392 67 62 3 1 392 67 1 1 43 6 3 41 3 6 3 92 6 7 6 58 43 60 37 6 7 5 78 92 6 7 7 43 8 779 3 6 3 5 1 8643 7 88 6 22 22 22 88 6 22 22 22 22 22 22 22 22 22 19 8 22 22 22 22 19 8...

Page 26: ...Control panel door 1 24 16 512 SSDP120 Hard wire door 1 25 16 527 SSDP120 Radiator door 1 26 16 511 SSDP120 Bund blank plate 1 27 16 506 SSDP120 Perkins 1104 radiator plate 1 28 16 530 SSD110 Air outl...

Page 27: ...8 27 26 25 30 3 40 33 37 38 39 9 18 15 R Golding A 13 10 15 New drawing Date Revision Issue THIRD ANGLE PROJECTION Description Fax Phone Drawing Number Drawn SSDP120 Canopy exploded view 16 548 STEPHI...

Reviews: