Enviro Maintenance Manual 2004
LV10 PANEL
LOCATED ON
KES FILTER
____ HP
EXHAUST FAN MOTOR
THREE WIRES FROM LV10 PANEL TO EXHAUST FAN MOTOR STARTER BY
MECHANICAL WHEN KES FAN AND FILTER SECTIONS ARE SPLIT 120V/1/60, 5 AMPS
TEN (10) WIRES TO THE
RPW10 - 120V/1/60 - 10 AMPS.
TO REMOTE CONTROL STATION LOCATED IN
IN THE KITCHEN AREA MODEL RPD10 OR
1&4
15
18
16
17
12
14
13
5
14
TERMINAL
18
16
17
15
5
13
12
1
4
POWER FROM RPD10
KES FAN/NORMAL OPERATION
BAG FILTER CLOGGED
FIRESTAT - HIGH LIMIT
0DOR SPRAY UNIT
FILTER OUT/LOW AIR
BOX FILTER CLOGGED
PREFILTER CLOGGED
LV10 RESET
DESCRIPTION
LEGEND
RESET
1
UNIT
ENCLOSURE
TRANSFORMER
DISCONNECT
30 AMP
EEMAC3R
T2
L2
T 2
L2
T3
M1
WIRING HARNESS IN
MOTOR STARTER
120V
XXXV
L3
7
1 3
6
95
G1
96
T 3
A2
L3
A 1
T1
KES TELE MOTOR STARTER
IN EEMAC4 ENCLOSURE
MOUNTED ON FAN UNIT
L1
EEMAC4
M1
T 1
O/L
L1
FILTER REMOVED SWITCHES
EXHAUST INLET SET AT 225 °F
HI TEMP STAT LOCATED IN THE
P5 - BOX FILTERS (SET AT 0.25" W.C.)
P4 - BAG FILTERS (SET AT 0.25" W.C.)
TH1
P5
P4
FILTER CLOGGED PRESSURE SWITCHES
P2 - BAG FILTER (SET AT 1.0" W.C.)
P1 - PREFILTER (SET AT 1.0" W.C.)
P3 - BOX FILTER (SET AT 1.2" W.C.)
P2
P3
P1
17
TO THE ODOUR CONTROL UNIT 120V/1/60
4.2 AMPS. MAXIMUM. WIRES BY SPRING AIR
WIRING FROM EXHAUST FAN MOTOR STARTER
4
LOCATED ON KES FAN SECTION
OPTIONAL ODOUR CONTROL PANEL
TO FACTORY MOUNTED BASEBOARD HEATER
WITH THERMOSTAT FOR SPRAY ENCLOSURE
____ FLA
POWER SUPPLY
____V/3/60
CONTROL WIRING BY MECHANICAL CONTACTOR
FACTORY WIRING BY SPRING AIR SYSTEMS
POWER WIRING BY GENERAL CONTRACTOR
KESF FAN SECTION
KES-ISH FILTER SECTION
Wiring diagram for Outdoor KES, motor starter, LV10 J-Box, and odor unit
Figure 21