Enviro Maintenance Manual 2004 

KES ENVIRO START-UP REPORT  

Job Name 

 

Date 

 

Location 

 

File No. 

 

KES No. 

 

Motor HP 

 

S/N 

 

Voltage 

 

 

Item 

Description 

Y / N 

Check all electrical connections.  Tighten as necessary 

 

(RPD10 panels only) Check for power to the RPD10 panel on terminals 1 & 4 

 

2a 

Check all remote wiring to ensure it has been connected 

 

(RPW10 panels only)  Check wiring to terminals 1, 3 & 4 from water wash panel to RPW10 remote 

 

LV10 J-Box wiring to terminal 1, 4 & 5 from RPD10- or RPW10 remote 

 

LV10 J-Box wiring to terminal 4 & 5 to exhaust fan motor starter 

 

LV10 J-Box wiring to odor spray 4 & 17 (Optional for odor spray units)  

 

Power wiring to disconnect switch 

 

Check if all filters are in the unit 

Type of Filter 

Size 

Qty 

Prefilter 

12” x 24” x 2” 

 

Prefilter 

24” x 24” x 2” 

 

10 

Bag Filter 

12” x 24” x 22” 

 

11 

Bag Filter 

24” x 24” x 22” 

 

12 

Box Filter 

12” x 24” x 12” 

 

13 

Box Filter 

24” x 24” x 12” 

 

 

Item 

Decryption 

Y / N 

14 

Check of the inlet exhaust ductwork to the KES unit from the kitchen exhaust hood is all welded NFPA-96

 

15 

Check if clearance to top, sides, and ends of KES filter box is available: 18” to combustible or 6” to non-
combustibles 

 

16 

Check power at disconnect switch 

3/60/            V 

 

17 

Check fan rotation as follows:  
Turn on the main disconnect to the KESF fan motor starter   
Turn “FAN ON” switch in the wash panel or remote RPD10 panel to the ON position 
Turn on the Override switch in the RPD10 or RPW10 remote panel.  The LOGO text message “Service 
Filters within 4 hours” will appear.  
Turn “FAN OFF” switch in the wash panel or remote RPD10 panel to the OFF position.   Observe the fan 
rotation.  Change one of L1, L2 or L3 if fan is rotating backwards 

 

 

Item 

Description 

Y / N 

18 

Turn “FAN ON” switch in the wash panel or remote RPD10 panel to the ON position 

 

19 

Check the FLA 

L1 

L2 

L3 

 

20 

Adjust the overload setting on motor starter to FLA rating of motor 

 

Safety Circuit Check 
21 

Turn “FAN OFF” switch in the wash panel or remote RPD10 panel to the OFF position 

 

22 

Rotate the OVERRIDE switch on the RPD10 or RPW10 to the original position.  The text message will 
disappear once the fan is turned back on. 

 

23 

Remove the front covers from all the pressure switches on the KES-ISH filter box. 

 

24 

Turn “FAN ON” switch in the wash panel or remote RPD10 panel to the ON position 

 

Switch P1 
25 

Jumper switch P1– terminals 1 & 12 

26 

KES unit shuts off 

Yes 

No 

27 

Prefilter clogged light on and LOGO text message “Change Prefilter” 

Yes 

No 

28 

Reset unit at LV10 J-Box reset switch by turning on and off 

Switch P2 
29 

Jumper switch P2– terminals 1 & 13 

30 

KES unit shuts off 

Yes 

No 

31 

Bag clogged light on and LOGO text message “Change Bag filter” 

Yes 

No 

32 

Reset unit at LV10 J-Box reset switch by turning on and off 

Switch P3 
33 

Jumper switch P3– terminals 1 & 14 

34 

KES unit shuts off 

Yes 

No 

35 

Box clogged light on and LOGO text message “Change Box Filter” 

Yes 

No 

36 

Reset unit at LV10 J-Box reset switch by turning on and off 

 

 
 
 
 

Summary of Contents for KES Enviro

Page 1: ...KES Enviro Maintenance Manual ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179 info springairsystems com...

Page 2: ......

Page 3: ...or AP MP Panels 4 Filter Hood or Dry Grease Extractor 5 Control Circuit 7 Setting the Day and Time 13 Setting the Weekday Fan ON and OFF Times 14 Setting Weekend Operation 15 Odor Spray Systems 15 Whe...

Page 4: ......

Page 5: ...ries Inc UL listing allows the kitchen exhaust air to be discharge to atmosphere at low levels Prior to any installation the installer must seek approval from the authorities having jurisdiction THE S...

Page 6: ...L E C T R I A L W I R I N G A N D N A T I O N A L C O D E R E Q U I R E M E N T S S H A L L C O N F O R M T O A L L L O C A L N O T E 1 I N T E R N A L W I R I N G B Y S P R I N G A I R C U R C U I T...

Page 7: ...S TO THE WET CHEMICAL SWITCH 120V 1 60 1 AMP MOTORIZED INLET DAMPER AND END OPTIONAL THREE 3 WIRES TO OPTIONAL POWER SUPPLY TO SUPPLY FAN MOTOR STARTER 120V 1 60 2 AMPS DRY CONTACT FOR BUILDING FIRE A...

Page 8: ...ses and sends power through terminals 3 4 to the RPW10 remote panel to energize the exhaust fan through terminals 5 4 in the LV 10 J Box The LV10 J Box is mounted on the KES ISH filter section The NOR...

Page 9: ...1 2 ESC OK 1 Q 3 1 Q 1 1 2 Q4 1 2 Q2 15 AMP CURCUIT BREAKER AUX FAN SWITCH I4 I2 L N I1 I3 01 20 03 Mo 09 00 I 5 I 6 I7 I8 L N OVERIDE SWITCH OFF ON RPD10A ELECTRICAL DATA I 1 I 2 I 3 I 4 RUN STOP BOX...

Page 10: ...Internal Wiring Figure 10 REMOVED WARNING CLOGGED BOX FILTER FILTER OVERIDE BAG FILTER CLOGGED PREFILTER CLOGGED NORMAL FIRE IN PANEL BACK HOLES LOCATED PANEL MOUNTING KES OFF ON FILTER 8 0 14 0 5 RPD...

Page 11: ...C P4 BAG FILTER REMOVED SWITCH COPPER TUBING REMOVED SWITCH SECTION TO RIGHT OF BOX FILTER ACCESS DOOR PRESSURE SWITCHES LOCATED ON KES ISH FILTER BOX P5 B A G P4 P 3 P2 PREFILTER P 1 Pressure Switch...

Page 12: ...P4 BAGFILTERS SETAT0 25 W C L1 O L L2 L3 T1 T3 T2 A1 A2 6 3 7 M1 WIRINGHARNESSIN MOTOR STARTER THREE WIRES FROM LV10 PANEL TO EXHAUST FAN MOTOR STARTER BY MECHANICAL WHEN KES FAN AND FILTER SECTIONS A...

Page 13: ...he KES unit or within the KES unit a firestat located at the inlet of the KES filter section is activated When the exhaust air reaches 160 F the firestat is energized The exhaust fan shuts off the NOR...

Page 14: ...osition Figure 17 System Reset After any of the safety circuit annunciation the system must be reset The system is reset by toggling the RESET switch in the LV10 J box or switching the OVERRIDE SWITCH...

Page 15: ...Enviro Maintenance Manual 2004 RPD10 Face Plate Figure 19 RPW10 Face Plate Figure 20...

Page 16: ...3 7 1 3 6 95 G1 96 T 3 A2 L3 A1 T1 KES TELE MOTOR STARTER INEEMAC4ENCLOSURE MOUNTED ON FAN UNIT L1 EEMAC4 M1 T 1 O L L1 FILTER REMOVED SWITCHES EXHAUSTINLETSETAT225 F HI TEMP STAT LOCATED IN THE P5 BO...

Page 17: ...01 00 Th 00 00 Su 06 16 01 01 00 MM DD YY Set Clock Set Clock MM DD YY 01 01 00 Th 00 00 Set Clock Su 00 00 01 01 00 MM DD YY Prg Name Set Clock Set Parma Set Clock Set Parma Prg Name Stop to return...

Page 18: ...Press to remove Monday from the weekly schedule The dash indicates The cursor will move to M Monday 5 The clock has been factory set to turn the fan on at 6 00 a m and off 8 Press to move to the next...

Page 19: ...ess If your selection is complete press and to return the 9 Press operating screen 10 You have completed programming weekend fan On and Off cycling 01 06 03 Su 06 16 B04 No2 On 10 00 D SS B04 No2 Off...

Page 20: ...g the setting by is not adequate decrease the cycle to of the original setting If this is not adequate adjust the spray timer B02 a Increase the spray time B02 in increments of 5 seconds After each 5...

Page 21: ...s are minutes and the two digits to the right are seconds Press to change the cycle length in minutes Press to move to the T 05 00m 9 To change spray time press 11 Press if the cycle time is correct 8...

Page 22: ...tlet valves are interchangeable Clean them with water When replacing the outlet valve place the new valve in location and note there is a retaining bar near the machine screw hole This retaining bar h...

Page 23: ...x 24 x 22 V9 4M Class II American Air Filter 24 x 24 x 21 DRI PAK Class II 12 x 24 x 21 DRI PAK Class II Farr Filters 24 x 24 x 22 90 ASHRAE 52 76 Class II 12 x 24 x 22 90 ASHRAE 52 76 Class II BOX F...

Page 24: ...oved pressure switch The switch must make and close after 30 seconds of operation Adjust the pressure setting or replace switch i If all the filters are in place check if pressure tips on the end of t...

Page 25: ...pen Replace if necessary V Fire Pilot On 1 The fire stat in the KES filter section exhaust outlet has activated and shut the KES system down If a fire is not present check calibration of firestat TH1...

Page 26: ...system For heavy cooking applications the bag filters may require replacement every month 4 Odor Spray Option Inspect the odor spray bottle Refill if necessary At startup the odor spray is adjusted t...

Page 27: ...years of service under most conditions 2 Re greasing of motors depends on the application and is best left to trained service technicians 3 Periodically check if motor is running hotter then normal C...

Page 28: ...Turn on the Override switch in the RPD10 or RPW10 remote panel The LOGO text message Service Filters within 4 hours will appear Turn FAN OFF switch in the wash panel or remote RPD10 panel to the OFF p...

Page 29: ...sted With the filters out rotate the pressure adjustment screw slowly clock wise until the unit shuts off Fire Switch Test 41 Jumper terminals 1 16 in the LV10 J Box 42 KES unit shuts off Yes No 43 Fi...

Page 30: ...nance Manual 2004 FILTER FREQUENCY CHART Enter the date of each filter change Startup date Change No Prefilter Bag Filter Box Filter Odor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24...

Page 31: ...ater Wash Cold Water Spray Hot Water Wash Water Wash Control Panels Dry Ventilators REV LOW Hood Filter Hoods Surface Fire Suppression Commercial Kitchen Exhaust Fans Kitchen Enviro Systems KES 100 Ex...

Reviews: