Enviro Maintenance Manual 2004
Remote wiring of KES Enviro units with Dry Hood
Figure 12
CONTROL CIRCUIT
Filter Clogged:
During normal operation of the KES unit three-filter stages collect grease, dust, and lint particulate. The type
of cooking equipment and the hours of operation determines the useful life of the individual filters.
(SET AT 1.2 in. W.C.)
(SET AT 1.0 in. W.C.)
(SET AT 1.0 in. W.C.)
P 1 - P L E A T E D F I L T E R
C L O G G E D S W I T C H
P3 - BOX FILTER
C L O G G E D S W I T C H
P2 - BAG FILTER
C L O G G E D S W I T C H
F I L T E R
FILTER
(SET AT 0.25 in. W.C.)
P 5 - B O X F I L T E R
(SET AT 0.25 in. W.C.)
P4 - BAG FILTER
REMOVED SWITCH
C O P P E R T U B I N G
REMOVED SWITCH
S E C T I O N T O R I G H T O F B O X F I L T E R A C C E S S D O O R
P R E S S U R E S W I T C H E S L O C A T E D O N K E S - I S H F I L T E R
BOX
P5
B A G
P4
P 3
P2
P R E F I L T E R
P 1
Pressure Switch Locations
Figure 13
T O R P D 1 0 R E M O T E
I N T E R L O C K B E T W E E N K E S - I S H L V 1 0 A N D K E S F M O T O R S T A R T E R
P O W E R S U P P L Y
K E S - I S H
T O K E S F F A N U N I T
P O W E R S U P P L Y
K E S F
D U C T W O R K
E X H A U S T D I S C H A R G E
D U C T W O R K A S R E Q U I R E D
F I E L D I N T E R C O N N E C T I N G
J - B O X - 1 2 0 V / 1 / 6 0
E X H A U S T I N L E T
F R O M T H E K E S - I S H L V 1 0
T H E R P D 1 0 C O N T R O L L E R
T E N ( 1 0 ) W I R E S F R O M
D U C T W O R K
R P D 1 0
C O N T R O L L E R
Summary of Contents for KES Enviro
Page 2: ......
Page 4: ......
Page 15: ...Enviro Maintenance Manual 2004 RPD10 Face Plate Figure 19 RPW10 Face Plate Figure 20...