Enviro Maintenance Manual 2004
KES ENVIRO STARTUP REPORT page 2
Switch P4
33
Jumper switch P4
34
KES unit shuts off
Yes
No
35
Filter removed light on and LOGO text message “Filter Out or Low Exhaust”Yes
No
36
Reset unit at LV10 J-Box reset switch by turning on and off
Switch P5
33
Jumper switch P5
34
KES unit shuts off
Yes
No
35
Filter removed light on and LOGO text message “Filter Out or Low Exhaust”Yes
No
36
Reset unit at LV10 J-Box reset switch by turning on and off
Filter Out Test #1
33
Replace pressure switch covers and turn of the unit and remove all the bag filters. Shut the access door and turn the
unit on. Wait for 30 sec.
34
KES unit shuts off
Yes
No
35
Filter removed light on and LOGO text message “Filter Out or Low Exhaust”Yes
No
36
Reset unit at LV10 J-Box reset switch by turning on and off
Filter Out Test #2
37
Replace pressure switch covers and turn of the unit and remove all the box filters. Shut the access door and turn the
unit on. Wait for 30 sec.
38
KES unit shuts off
Yes
No
39
Filter removed light on and LOGO text message “Filter Out or Low Exhaust”Yes
No
40
Reset unit at LV10 J-Box reset switch by turning on and off
If the unit does not shut off and the filter clogged light does not come on for this test the pressure switch setting must
be adjusted. With the filters out rotate the pressure adjustment screw slowly clock wise until the unit shuts off.
Fire Switch Test
41
Jumper terminals 1 & 16 in the LV10 J-Box.
42
KES unit shuts off
Yes
No
43
Fire light on
Yes
No
44
Reset unit at LV10 J-Box reset switch by turning on and off
Check override switch
45
Turn “FAN OFF” switch in the wash panel or remote RPD10 panel to the OFF position
46
Jumper terminals 1 & 12
47
Turn “FAN ON” switch in the wash panel or remote RPD10 panel to the ON position
48
After 30 seconds the KES shuts off, the Prefilter Clogged light turns on and the LOGO text message “Prefilter Clogged”
will appear.
49
Rotate the OVERRIDE switch on the RPW10 or RPD10 remote panel to the ON position.
50
KES unit turns on
Yes
No
51
Warning light turns on and the LOGO text message “Service Filters within 4
hours” will appear.
Yes
No
52
Turn “FAN OFF” switch in the wash panel or remote RPD10 panel to the OFF position
53
Remove the jumper
54
Turn “FAN ON” switch in the wash panel or remote RPD10 panel to the ON position
55
Rotate the OVERRIDE switch on the RPW10 or RPD10 remote panel to the OFF position. The Warning light goes off
and the LOGO text message disappears.
56
Measure the exhaust air volume at each hood
Use hood start up form for this
Comments:
Service Technician:_____________________________________________________________
Yes I have received a set of Spring Air Systems Inc. maintenance manuals.
Signature ___________________ Print Name ____________________