background image

 

Enviro Maintenance Manual 2004 

ODOR SPRAY SYSTEM 

Operating and Maintenance 

The Spring Air Systems Inc. odor spray unit has a one-year warranty from startup.  The two timers, cycle 
timer B01, and spray timer B02, are factory set (5 minute cycle and 2 second spray) and then adjusted 
during startup to the odor reducing intensity required for the application.  The B01 cycle timer is generally set 
between 5 to 10 minutes.  The B02 spray timer is generally set between 2 to 60 seconds. 
 

How does it Work? 

The odor spray setting is a qualitative measurement.  The spray timers are field set to provide adequate 
odor reduction for the installation.  This is completely subject to what a particular person feel is an 
acceptable discharge odor. 
 
During the spray timer activation the combination air compressor and air-atomizing nozzle injects a volume 
of odor solution into the exhaust discharge.  This solution is carried along the discharge duct and vented to 
atmosphere.  The spray solution chemically activates with the kitchen exhaust air to reduce the kitchen 
exhaust odors.  As the solution is carried down the duct some adheres to the duct walls.  We will call this the 
spray residue.  During the cycle time when the spray is not activated this spray residue continues the odor 
reducing process as the exhaust air passes.  Therefore installation with longer discharge ducts can normally 
use a longer cycle time because there will be more spray residue.  A shorter run of discharge duct usually 
results in shorter cycle time. 
 
A.  When adjusting the timers the object is to use as little spray solution as possible to provide adequate 

odor reduction: 

 

1.  First adjust the spray cycle, B01 timer.   
2.  Reduce this setting  by ½ of the original cycle setting and check the operation.  If ½ proves 

adequate, increase the cycle back to ¾ of the original cycle setting.  If this is adequate increase to 
7/8 of the original setting and so forth.   

3.  If reducing the setting by ½ is not adequate decrease the cycle to ¼ of the original setting.  If this is 

not adequate adjust the spray timer B02. 

a.  Increase the spray time B02 in increments of 5 seconds.  After each 5 second increase 

evaluate the quality of the exhaust discharge air to determ ine if it is acceptable to the user. 

b.  When the spray timer setting equals the cycle timer settings the spray will be continuous. 

The maximum setting of B02 should not exceed the cycle timer B01. 

 
The odor spray bottle must be changed regularly depending on the length of time set on timers B01 and 
B02.  The odor spray line from the spray bottle to the spray nozzle must be cleaned every 6 months in a 
water and detergent mixture.  The compressed air gauge should read between 10 and 15 psi.  When the air 
gauge i s reading below 10 psi clean out the compressed air line.  If the pressure is still low proceed to the 
next step compressor maintenance. 
 

When there is odor in adjoining floors or office spaces 

A kitchen located in the interior of an office building must be very negative to keep the kitchen odor within 
the kitchen.  We recommend the kitchen be a minimum 20% negative.  The fresh air supply is 80% of the 
total exhaust air from the kitchen space.  When there is odor in adjoining spaces check the following. 
 

1.  The kitchen is not negative enough to keep the smell of the kitchen in the kitchen.  If this is the 

case the odor is usually present all the time, even when there is no cooking.  Reduce the amount of 
fresh air to the kitchen by adjusting the supply fan volum e. 

2.  The kitchen may be connected to the same building A/C unit as the rest of the floor.  If this is the 

case the return air grilles in the kitchen draws the kitchen odor to the main A/C unit and disperses 
the odor throughout the floor.  The main A/C return must be blocked from the kitchen and put on a 
separate A/C unit. 

3.  The floor above the kitchen have odor.  There are three possibilities. 

a.  The exhaust shaft is not sealed and the kitchen exhaust is leaking out onto the floors 

above the kitchen.  Either adjus t the amount of odor spray per section "A" above or install 

Summary of Contents for KES Enviro

Page 1: ...KES Enviro Maintenance Manual ___________________________ Spring Air Systems Inc Oakville Ontario Phone 905 338 2999 Fax 905 338 0179 info springairsystems com...

Page 2: ......

Page 3: ...or AP MP Panels 4 Filter Hood or Dry Grease Extractor 5 Control Circuit 7 Setting the Day and Time 13 Setting the Weekday Fan ON and OFF Times 14 Setting Weekend Operation 15 Odor Spray Systems 15 Whe...

Page 4: ......

Page 5: ...ries Inc UL listing allows the kitchen exhaust air to be discharge to atmosphere at low levels Prior to any installation the installer must seek approval from the authorities having jurisdiction THE S...

Page 6: ...L E C T R I A L W I R I N G A N D N A T I O N A L C O D E R E Q U I R E M E N T S S H A L L C O N F O R M T O A L L L O C A L N O T E 1 I N T E R N A L W I R I N G B Y S P R I N G A I R C U R C U I T...

Page 7: ...S TO THE WET CHEMICAL SWITCH 120V 1 60 1 AMP MOTORIZED INLET DAMPER AND END OPTIONAL THREE 3 WIRES TO OPTIONAL POWER SUPPLY TO SUPPLY FAN MOTOR STARTER 120V 1 60 2 AMPS DRY CONTACT FOR BUILDING FIRE A...

Page 8: ...ses and sends power through terminals 3 4 to the RPW10 remote panel to energize the exhaust fan through terminals 5 4 in the LV 10 J Box The LV10 J Box is mounted on the KES ISH filter section The NOR...

Page 9: ...1 2 ESC OK 1 Q 3 1 Q 1 1 2 Q4 1 2 Q2 15 AMP CURCUIT BREAKER AUX FAN SWITCH I4 I2 L N I1 I3 01 20 03 Mo 09 00 I 5 I 6 I7 I8 L N OVERIDE SWITCH OFF ON RPD10A ELECTRICAL DATA I 1 I 2 I 3 I 4 RUN STOP BOX...

Page 10: ...Internal Wiring Figure 10 REMOVED WARNING CLOGGED BOX FILTER FILTER OVERIDE BAG FILTER CLOGGED PREFILTER CLOGGED NORMAL FIRE IN PANEL BACK HOLES LOCATED PANEL MOUNTING KES OFF ON FILTER 8 0 14 0 5 RPD...

Page 11: ...C P4 BAG FILTER REMOVED SWITCH COPPER TUBING REMOVED SWITCH SECTION TO RIGHT OF BOX FILTER ACCESS DOOR PRESSURE SWITCHES LOCATED ON KES ISH FILTER BOX P5 B A G P4 P 3 P2 PREFILTER P 1 Pressure Switch...

Page 12: ...P4 BAGFILTERS SETAT0 25 W C L1 O L L2 L3 T1 T3 T2 A1 A2 6 3 7 M1 WIRINGHARNESSIN MOTOR STARTER THREE WIRES FROM LV10 PANEL TO EXHAUST FAN MOTOR STARTER BY MECHANICAL WHEN KES FAN AND FILTER SECTIONS A...

Page 13: ...he KES unit or within the KES unit a firestat located at the inlet of the KES filter section is activated When the exhaust air reaches 160 F the firestat is energized The exhaust fan shuts off the NOR...

Page 14: ...osition Figure 17 System Reset After any of the safety circuit annunciation the system must be reset The system is reset by toggling the RESET switch in the LV10 J box or switching the OVERRIDE SWITCH...

Page 15: ...Enviro Maintenance Manual 2004 RPD10 Face Plate Figure 19 RPW10 Face Plate Figure 20...

Page 16: ...3 7 1 3 6 95 G1 96 T 3 A2 L3 A1 T1 KES TELE MOTOR STARTER INEEMAC4ENCLOSURE MOUNTED ON FAN UNIT L1 EEMAC4 M1 T 1 O L L1 FILTER REMOVED SWITCHES EXHAUSTINLETSETAT225 F HI TEMP STAT LOCATED IN THE P5 BO...

Page 17: ...01 00 Th 00 00 Su 06 16 01 01 00 MM DD YY Set Clock Set Clock MM DD YY 01 01 00 Th 00 00 Set Clock Su 00 00 01 01 00 MM DD YY Prg Name Set Clock Set Parma Set Clock Set Parma Prg Name Stop to return...

Page 18: ...Press to remove Monday from the weekly schedule The dash indicates The cursor will move to M Monday 5 The clock has been factory set to turn the fan on at 6 00 a m and off 8 Press to move to the next...

Page 19: ...ess If your selection is complete press and to return the 9 Press operating screen 10 You have completed programming weekend fan On and Off cycling 01 06 03 Su 06 16 B04 No2 On 10 00 D SS B04 No2 Off...

Page 20: ...g the setting by is not adequate decrease the cycle to of the original setting If this is not adequate adjust the spray timer B02 a Increase the spray time B02 in increments of 5 seconds After each 5...

Page 21: ...s are minutes and the two digits to the right are seconds Press to change the cycle length in minutes Press to move to the T 05 00m 9 To change spray time press 11 Press if the cycle time is correct 8...

Page 22: ...tlet valves are interchangeable Clean them with water When replacing the outlet valve place the new valve in location and note there is a retaining bar near the machine screw hole This retaining bar h...

Page 23: ...x 24 x 22 V9 4M Class II American Air Filter 24 x 24 x 21 DRI PAK Class II 12 x 24 x 21 DRI PAK Class II Farr Filters 24 x 24 x 22 90 ASHRAE 52 76 Class II 12 x 24 x 22 90 ASHRAE 52 76 Class II BOX F...

Page 24: ...oved pressure switch The switch must make and close after 30 seconds of operation Adjust the pressure setting or replace switch i If all the filters are in place check if pressure tips on the end of t...

Page 25: ...pen Replace if necessary V Fire Pilot On 1 The fire stat in the KES filter section exhaust outlet has activated and shut the KES system down If a fire is not present check calibration of firestat TH1...

Page 26: ...system For heavy cooking applications the bag filters may require replacement every month 4 Odor Spray Option Inspect the odor spray bottle Refill if necessary At startup the odor spray is adjusted t...

Page 27: ...years of service under most conditions 2 Re greasing of motors depends on the application and is best left to trained service technicians 3 Periodically check if motor is running hotter then normal C...

Page 28: ...Turn on the Override switch in the RPD10 or RPW10 remote panel The LOGO text message Service Filters within 4 hours will appear Turn FAN OFF switch in the wash panel or remote RPD10 panel to the OFF p...

Page 29: ...sted With the filters out rotate the pressure adjustment screw slowly clock wise until the unit shuts off Fire Switch Test 41 Jumper terminals 1 16 in the LV10 J Box 42 KES unit shuts off Yes No 43 Fi...

Page 30: ...nance Manual 2004 FILTER FREQUENCY CHART Enter the date of each filter change Startup date Change No Prefilter Bag Filter Box Filter Odor 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24...

Page 31: ...ater Wash Cold Water Spray Hot Water Wash Water Wash Control Panels Dry Ventilators REV LOW Hood Filter Hoods Surface Fire Suppression Commercial Kitchen Exhaust Fans Kitchen Enviro Systems KES 100 Ex...

Reviews: