Chapter 3: Configuring the 2085-IF4XOF4-SC Using CCW
3-13
User’s Manual Pub. 0300307-01 Rev. A
3.5.3
Startup and Factory Default Conditions
After the module boots and before the initial configuration is received, the
module holds the default configuration as specified in the Configuration
Assembly. There is no input data communication and no signal outputting before
the controller goes into run mode. The initial configuration assumes a default
configuration of 0 to 20 mA for current settings and
±
10 V for all voltage settings
for both input measurement and channel outputting.
PLC Interfaces
3.6.1
Module Identity
Parameter
Description
Vendor ID
58 (Spectrum Controls)
Product Type
10 (Analog)
Product Code
114
Series Rev
50208 (First release revision is 1.1)
Module Catalog String 2085-IF4XOF4-SC
3.6.2
Connection Types and Assembly Sizes
The size of each assembly is listed in the table below. Each word takes 2 bytes.
Assembly Table Size (words)
Configuration
16
Input
14
Output
5