1-8
Chapter 1, Module Overview
User’s Manual Pub. 0300307-01 Rev. A
Environmental Specifications
The 2085-IF4XOF4-SC module has the following environmental specifications:
Table 1-4. EMC Specification Table
Environmental Tests
Industry Standards
Radiated Emissions
(Enclosure) Class A, 30 MHz – 1 GHz
Conducted Emissions
Group 1, Class A (AC Mains), 150 kHz – 30 MHz
ESD immunity
(Performance Criteria B)
6 kV Indirect (Coupling Plate)
6 kV Contact Discharge (to points of initial contact)
8 kV Air Discharge (to points of initial contact)
Radiated RF immunity
(Performance Criteria A)
10 V/M with 1 kHz sine-wave 80% AM from 80…2000 MHz
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at 900
MHz
10 V/M with 200 Hz square-wave 50% Pulse 100% AM at 1890
MHz
10 V/M with 1 kHz sine-wave 80% AM from 1400…2000 MHz
10 V/M with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
(Performance Criteria B)
Signal Ports:
± 2 kV at 5 kHz for 5 minutes, Criteria B
Power Ports:
± 2 kV at 5 kHz for 5 minutes, Criteria B
Surge transient immunity
(Performance Criteria B)
Signal Ports:
± 2 kV line-earth {CM}at
2Ω on shielded ports
Power Ports
± 2 kV CM at
12Ω
± 1 kV DM at
2Ω
Conducted RF immunity
(Performance Criteria A)
10 V RMS with 1 kHz sine wave 80% AM from 150 kHz…80
MHz on signal and power ports
Magnetic Field
(Performance Criteria A)
30 ARMS/m
Input Description
Specification
Input Bias Currents and Impedance
Open Wire Detection Current
(Voltage range only)
Approximately 100 µA during open wire checks for a duration of
one channel scan time, with a 470 Hz filter.
Current input impedance
250 (±10%) ohm
Voltage input impedance
15 Mohms except during open circuit detection
Summary of Contents for 2085-IF4XOF4-SC
Page 1: ......
Page 8: ...viii Micro800TM Analog Combination I O Module User s Manual Pub 0300307 01 Rev A...
Page 20: ...1 12 Chapter 1 Module Overview User s Manual Pub 0300307 01 Rev A...
Page 62: ...3 34 Chapter 3 Configuring the 2085 IF4XOF4 SC Using CCW User s Manual Pub 0300307 01 Rev A...