Range Type and its limits for Output and Input Channels
Range Types
For module outputs, this module has one 4-channel DAC equipped with 4
programmable output drivers. For module inputs, multiplexed ADC and PGA are
used. Both are configured and set based on user-configurable parameters.
There are five pre-defined Range Type Format settings used for Output and Input
Channels. Range types for output and input channels are:
Index Range Type Note
0
0 to 20 mA
Default
1
4 to 20 mA
2
-10 to 10 V
3
0 to 10 V
4
0 to 5 V
The final current or voltage output signal and input signal are determined by:
•
Range.
•
Data Format (fixed or user-defined).
•
Output Word (Output channel only).
•
ADC Filter (Input channel only).
•
Operational state of the module:
-
Run
-
Program
-
Fault
Range Limits by Software Controls
Regardless of the final scaled value, the output and input signals clipped to a
High and Low Limit by software are based on the following table:
•
The High and Low Range values indicate the intended use of the Range.
•
The Current Ranges allow for a 2% overhead at each Range endpoint.
•
The Voltage Ranges allow for a 5% overhead at each Range endpoint.
•
Ranges with a 0 mA or 0 V Low Range are clipped at 0 mA or 0 V and
do not go negative.
The following table provides range limits for input and output channels:
Range Type
Low Limit Low Range High Range High Limit
0 to 20 mA
0.0 mA
0.0 mA
+20.0 mA
+20.4 mA
4 to 20 mA
+3.92 mA
+4.0 mA
+20.0 mA
+20.4 mA
-10 to 10 V
-10.5 V
-10.0 V
+10.0 V
+10.5 V
0 to 10 V
0.0 V
0.0 V
+10.0 V
+10.5 V
0 to 5 V
0.0 V
0.0 V
+5.0 V
+5.25 V