Chapter 1: Module Overview
1-9
User’s Manual Pub. 0300307-01 Rev. A
Environmental Tests
Industry Standards
AC Mains Voltage Dips,
Interruptions and Variations
Follow the IEC 61000-4-11
Safety Test Specifications
The 2085-IF4XOF4-SC module has the following safety test specifications:
Table 1-5. Safety Test Specification Table
Safety Tests
Industry Standards
UL Safety
UL 61010-2-201 Safety Requirements for Electrical Equipment
for Measurement, Control, and Laboratory Use - Part 2-201:
Particular Requirements for Control Equipment (NRAQ,
NRAQ7)
cUL CAN/CSA C22.2 No. 61010-1-12 (Safety Requirements
for Electrical Equipment for Measurement, Control,
and Laboratory Use – Part 1: General Requirements)
UL Hazardous Locations
ULH ANSI/ISA–12.12.01–2007 Nonincendive Electrical
Equipment for Use in Class I, Division 2 Hazardous (Classified)
Locations (NRAG)
cULH CSA C22.2 No. 213-M1987 - Non-incendive Electrical
Equipment for use in Class I Division 2 Hazardous Locations -
March 1987 (NRAG7)
Temp code T4A, Pollution degree 2, gas groups a, b, c, and d
CE EMC Directive
IEC 61131-2 Programmable Controllers: Third Edition 2007-02,
Clause 8
IEC 61000-6-2: Generic Industrial Immunity
IEC 61000-6-4: Generic Industrial Emissions
Hardware Features
1.7.1
Circuit Protections
Channels are wired as inputs and outputs. For channel outputs, this module can
detect an open circuit current loop on each channel in 4 to 20 mA range, current
mode, a short on an output pin in voltage mode, and over temperature conditions
in both current and voltage modes. For input measurement, open wire detection is
available in the form of open circuit inputs going over-range for the voltage and
current ranges.
All 4 input channels are protected at the maximum input voltage of ±24 V in
voltage mode and limit the input current between 30 mA and 60 mA at fault over
current condition in current mode.
Outputs are protected from electrostatic discharge up to 6 kV for indirect and
contact discharge, 8 kV for air discharge. A load resistance greater than 500 Ohm
also triggers this fault.
A short on an output pin in voltage mode is also detected, and output current is
then limited to less than 15 mA. A load less than 1 Kohm resistance also triggers
Summary of Contents for 2085-IF4XOF4-SC
Page 1: ......
Page 8: ...viii Micro800TM Analog Combination I O Module User s Manual Pub 0300307 01 Rev A...
Page 20: ...1 12 Chapter 1 Module Overview User s Manual Pub 0300307 01 Rev A...
Page 62: ...3 34 Chapter 3 Configuring the 2085 IF4XOF4 SC Using CCW User s Manual Pub 0300307 01 Rev A...