3-26
Chapter 3: Configuring the 2085-IF4XOF4-SC Using CCW
User’s Manual Pub. 0300307-01 Rev. A
•
The channel Under Range status bit is automatically cleared when the
channel reading is greater than the Low Range
•
The channel Over Range status bit is automatically cleared when the
channel reading is less than the High Range
3.7.4
Customizable Clamp Ranges and Alarms for Output Channels
In addition to using the basic Under/Over Range Alarm feature on monitoring
channel status based on the Low & High Ranges of the configured Data Format
and Range Type selections, for Output Channel control, you can set different
indications other than default ranges such as limits or user-defined clamp values.
Each Output Channel can control the Low and High Clamp options separately.
Low/High Clamp options for Output Channels are listed in the following table:
Index Clamp Option
Note
0
At Range
Default
1
At Limit
2
At User-defined Clamp value
•
If Option 0 is selected, the channel status indication is the same as
previous Under/Over Range Alarm feature. The Channel Under/Over
Range status, the Channel Fault and module fault bits on the Output
Channel Status (AI_02:01) are set if the Output Channel reading is
less/equal or greater/equal to the Low/High Range.
•
If Option 1 is selected, the same bits from above are set if the Output
Channel reading is less/equal or greater/equal to the Low/High Limit.
•
If Option 2 is selected, the same bits from above are set if the Output
Channel reading is less/equal or greater/equal to the user-defined Clamp
value.
15
For monitoring Output Channel status, this bit can also be latched as an alarm. See Alarm Latches for
Output Channels.