Form 43343050
Jan 2014
-41-
23.0)
REPLACING PARTS
ELECTRIC SHOCK & EXPLOSION HAZARD
Disconnect electrical power and gas supply before
servicing.
Failure to do so may result in death or serious injury.
Only use genuine Space-Ray replacement parts. Parts are available from the factory for replacement by a
licensed person. Refer to the Replacement Parts Guide in Section 25.0) for all replacement parts.
23.1)
REMOVING SPARK ELECTRODE
The main burner can be inspected without removing the burner housing from the heat exchanger tube.
4
6
5
3/16
1
(Access panel only opens to 90 .)
3
2
1.
Disconnect electrical supply and open access panel.
2.
Pull out the ignition cable hooked to spark electrode.
3.
Remove two mounting screws.
4.
Take out the spark electrode. Check that the spark gap is 3/16”.
5.
Check spark electrode. Spark electrode should be clean and free from debris.
6.
Check ceramic on the spark electrode. It should be free from cracks.
23.2)
REMOVING MAIN BURNER AND GAS VALVE
4
3
5
6
1
2
1.
Disconnect electrical supply and gas connection at the restrainer nipple.
2.
Open the access panel and disconnect the wires from gas valve.