Form 43343050
-26-
Jan 2014
15.0)
ELECTRICAL CONNECTIONS
Failure to do so may result in death or serious injury.
This appliance must be connected to a properly grounded electrical source.
Disconnect electrical power and gas supply before servicing.
ELECTRIC SHOCK HAZARD
1.
All electric wiring shall conform to the latest edition of the National Electrical Code (ANSI/NFPA No. 70), or
the code legally authorized in the locality where the installation is made.
2.
The unit must be electrically grounded in accordance with the National Electrical Code (ANSI/NFPA No.
70-latest edition). In Canada, refer to current standard C22.1 Canadian Electrical Code Part 1.
3.
The wiring providing power to the heater shall be connected to a permanently live electrical circuit, one that
is not controlled by a light switch.
4.
The power supply to the unit should be protected with a fused disconnect switch or circuit breaker. A service
switch, as required by local codes, shall be located in the vicinity of the heater (check local codes for
allowable distances) and should be identified as Heater Service Switch. All electrical wiring must be located
in accordance with the required Clearances to Combustibles from the heater as listed on the nameplate on
the heater.
5.
When connecting the supply circuit
supply circuit
supply circuit
supply circuit to the heater, wiring material having a minimum size of 14 AWG and a
temperature rating of at least 90
°
C shall be used.
Ground
Screw
Terminal
Block
L2
L1
INCOMMING
POWER SUPPLY
CONNECTION
Motor
GROUND
NEUTRAL
120V
1
2
Terminal
Terminal
Block
SJO Cable
Viewed From
Inside
Draft Inducer
Junction Box
Control
Box
24V
SJO
Cable
6.
Straight Configuration
Straight Configuration
Straight Configuration
Straight Configuration ONLY:
ONLY:
ONLY:
ONLY: The installer will provide type SJO wire cable having minimum size of 18 AWG
and connect the ends to the draft inducer junction box and the control box. Secure with 3/8” connectors as
previously described in the attachment of the control box and draft inducer. Connect wire leads as shown in
the Connection Wiring Diagram. The SJO cable should be located and secured to protect it from mechanical
damage.