Electrical connection
6
6.7 Installing the battery modules
Risk of burns!
Very high short-circuit currents are possible.
The following must be observed when working with the battery modules:
The battery module is activated when the fuse connector is plugged in. The
voltage runs between the plus and minus contacts of the battery module (nominal
voltage of battery modules: 51.2 V DC). The battery module is deactivated when
the fuse connector is unplugged. No voltage runs between the plus and minus
contacts of the battery module. If all interconnected battery modules are
deactivated, it is safe to work on a battery module.
When working on the DC circuit:
►
Set aside metal jewellery.
►
Switch off the storage system.
►
Switch off the series fuse.
►
Remove the orange fuse
connectors on all battery modules.
Damage to battery modules due to short circuit!
If a short circuit occurs when installing the battery modules despite great care to
avoid this, proceed as follows:
►
Do not install the affected battery modules under any circumstance.
►
Notify the service team.