Electrical connection
6 Electrical connection
Danger to life due to electrocution!
The following points must be observed when carrying out electrical work on the
storage system or on the electrical distributor:
►
Switch off the storage system.
►
Disconnect the relevant electrical circuits.
►
Secure against anyone switching on the device again.
►
Check that the device is disconnected from the power supply.
►
Only authorised electricians are permitted to carry out electrical work.
Touch voltage in the event of a fault
Danger to life due to electrocution!
►
Install residual current devices (RCDs) upstream of the storage system.
The rated differential current of the residual current device (RCD) must be
30 mA. The type of RCD used must be adapted to suit on-site conditions. If no
special type is required, a type A residual current device (RCD) can be used.
Observe the maximum line lengths.
None of the lines connected to the storage system (electrical power, Ethernet
line, Modbus line, other data lines, etc.) are allowed to exceed a maximum length
of 30 m.
page 26 of 63