The AC contactor should be placed between the inverter and the loads.
Do not connect the load to DO port directly.
The contactor is not supplied by the Solinteg. Connect the load to the
DO port of the inverter directly if the load is designed with a DI port.
When the controlled load is connected to ONGRID, the contactor
coil must also be connected to ONGRID. When the controlled load is
connected to BACKUP, the contactor coil must also be connected to
BACKUP.
NOTE
Generator Control
Figure 5-26 Generator Control connection diagram
When the "GEN signal" is active, the open contact (GS) will switch on (no voltage output).
NO(1)
CO
M(2)
G
S
Diesel generator