54
User Manual
MHT-4~20K series
⑥
After the inverter is started, please refer to the [QUICK USE GUIDE] which is attached to
the access to configure the inverter.
If the inverter does not work properly, check the country code and
battery ID Settings.
①
Select the safety code suitable for the country (region) where the
inverter is installed at.
②
Select the battery ID suitable for the battery is installed.
NOTE
CT AUTO TEST FUNCTION
MHT hybrid inverter has the function of detecting the installation
direction and phase sequence of CT. The system is installed, this function
can be enabled on the APP for detection.
NOTE
SOC RESET FUNCTION
When the inverter is turned on for the first time, the battery will be
automatically charged to calibrate the battery SOC. After the battery is
charged, this function will be turned off automatically (If you confirm
that it is not necessary, you can manually turn off the function. We
recommend to enable this function.)
If you need to calibrate the SOC during system use, you can manually
enable the function to calibrate the battery SOC on app or inverter
screen. After the battery is fully charged, the function is automatically
disabled again.
NOTICE
※ 6.4 Stop the Inverter
When turning off the inverter, please follow the steps below:
①
Shut down the inverter through the APP or the button on the display first.
②
Disconnect the breakers on the grid and load side.
③
Turn off the battery switch, and disconnect the DC breaker on the battery side (if any).
④
Wait 30 seconds and then turn the inverter DC switch to the “OFF” position. At this time,
there is remaining power in the inverter capacitor. Wait for 10 minutes until the inverter is
completely de-energized before operating.
⑤
Disconnect the AC and DC cables.