PVI 10KW / PVI 13KW / PVI 15KW Installation and Operation Manual
DOC-020028 rev 028
11
NOTE:
Always use all 4 mounting tabs if wall mounted.
NOTE:
The nearly 380 lb. weight of the inverter will exert as much as 100 lbs. per
bolt on the 4 wall mounts. Tension on the top bolts could also be 100 lbs.
Make sure an appropriate safety margin is used for both shear and tension of wall
mounting bolts, anchors or other attachments.
NOTE:
If the roof/floor mounting only uses the inverter’s mounting feet, be sure
you use all 4 available foot mount bolt positions. If a stand is used, be sure inverter
is securely mounted to stand, the stand is adequately designed for the unit’s weight
and the stand is adequately attached to the floor/wall or roof.
NOTE:
In the case of roof/floor mounting, temporary removal of disconnect doors
may facilitate easy wiring of the unit (only while wiring) however, only do so if
necessary and acceptable by local codes and applicable NEC (Canadian Electrical
Code) requirements related to your particular mounting configuration. (Do not ever
leave disconnect or main enclosure doors open when you are not actually working
on the unit.)
2.3
DC Electrical Connection and AC Connection to
Building and Electrical Utility Grid
Fig. 3 Simplified electrical connection diagram
PVI 10 KW
10KW