PVI 10KW / PVI 13KW / PVI 15KW Installation and Operation Manual
DOC-020028 rev 028
38
50
60
70
80
90
100
0.00
5.00
10.00
15.00
AC Power (kW AC)
O
ver
al
l E
ff
ici
en
cy D
C
(
P
V
)
to
A
C
(3
-p
h
a
s
e
) %
Fig. 13. PVI 10KW / PVI 13KW / PVI 15KW peak efficiency plot at 280VDC input and 25C
ambient temperature.
Pin assignment RS232 / RS485 (optional) and Internet Gateway connection
(front view of 8-pin communication connector on
inverter, and back of mating connector)
1
RS232 TXD
2
RS232 RXD
3
RS232 GND
4
RS485 A (optional)
5
RS485 GND (optional)
6
RS485 B (optional)
7
RS485 GND
8
NC
Mating AMPSEAL 8-pin connector, Tyco part#: 776286-1
AMSEAL crimp contact, Tyco part#: 770854-3
Please call for information on data logging options / wiring diagrams. See the Fat Spaniel manual if your inverter is
equipped with Fat Spaniel Inverter-Direct. If
Fat Spaniel or SolView gateway
is installed in the inverter, then the
Ethernet CAT5 cable can be routed through the grommet on the right side of the inverter. Any RS485 daisy-chain
connections to other inverters can also use the grommet. 208VAC inverters have an integrated gateway power supply
but 480VAC units have a 120VAC supply than needs to be wired through the grommet as well. Note that the
grommet can be replaced with a conduit fitting and conduit.