PVI 10KW / PVI 13KW / PVI 15KW Installation and Operation Manual
DOC-020028 rev 028
10
Fig. 2.2c PVI 10KW / PVI 13KW / PVI 15KW Mounting Diagram (standard side-facing
disconnects)
Mounting Details
Using the mounting diagram Fig. 2.2 (a & c), choose whether floor/roof, wall or stand mounting
will be used. A forward facing disconnect configuration is available as an option. This is
especially useful in locations where limited space if available side-to-side to allow NEC
(Canadian Electrical Code) clearance for the standard side facing disconnects. The inverter
includes mounting feet for attachment to floors, roofs/roof plates/roof pans or stands. It also
includes mounting tabs for wall mounting. You can also use a combination of both mounting
provisions. For example, 2 bolts in floor mount feet and 2 bolts in the wall mount tabs.
It is recommended to use galvanized grade 5 or better bolts or stainless steel bolts. The correct
bolt size is 3/8” (10mm) diameter. If wall mounting is used, be sure to verify sheer and pullout
strength of anchors or other wall attachments.
WARNING:
Severe injury or death could occur if the inverter mounting fails and the
unit falls on a person.