utility grid at phase L1’’. To overcome this issue we suggest the
‘’Maximum reverse power’’ be set to at least 200W and the
‘’Maximum reverse power tripping time’’ be set to 20 seconds.
To get to these settings open the inverters web interface. Click
on the ‘’Device Parameter’’ tab and then open the ‘’AC Side’’
and ‘’Power Monitoring’’ drop downs.
3.1.3.
Communication Cable Connection
It is recommended that CAT5e cable be used. The termination resistor
on the last battery should be ON, the rest should be OFF.
Note: When connecting multiple inverters refer to the inverter manual
for more information.
3.1.3.1.
Single inverter, Single battery
3.1.3.2.
Single inverter, multiple batteries