Maximum charging / discharging voltages for non supported devices.
-
Bulk charge (stop charging)
54.6V
-
Float charge (if applicable)
53.8V
-
Low battery discharge:
48V
Check that the Equalisation function is disabled, then verify if there is a voltage difference on
the inverter display and the battery terminals @0.3C discharge / charge current. If so adjust
the values above.
Please check if your inverter charger has been approved by Solar MD and it is
CAN bus compatible.
For the latest Solar MD installation documents go to:
https://www.solarmd.com/inverter-compatibility-solarmd