![Sola HD S5KC User Manual Download Page 78](http://html.mh-extra.com/html/sola-hd/s5kc/s5kc_user-manual_1312925078.webp)
7�0 SPECIFICATIONS
Table 27: SolaHD S5KC Specifications
10 Bay
16 Bay
12 Bay
16 Bay
10 Bay
16 Bay
Unit Size, Type
No Transformer
Transformer-based
No Transformer Dual Inverter
Frame Rating, kVA/kW
15/13.5
20/18
15/13.5
20/18
15/13.5
20/18
General & Environmental
Conducted and Radiated
EMC Levels
IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
Compliant Safety
Standards
IEC/EN/AS 62040-1:2008,
UL 1778 4th Ed and CSA 22�2 No� 107�3
UL 1778 4th Ed and
CSA 22�2 No� 107�3
Compliant Immunity
Standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Transportation
Individual packaged modules meet ISTA-1A / 1B; the complete system meets ISTA-1E
Environmental
WEEE and ROHS2 (6 by 6), REACH Compliant
Protection Degree
IEC60529
IP 20
Color
RAL 7021
Dimensions, W x D x H, in (mm)
17x32x27
(440x800x695)
17x34x38
(440x850x970)
17x32x42
(440x800x1060)
17x34x49
(440x850x1240)
17x32x27
(440x800x695)
17x34x38
(440x850x970)
Weight, lb. (kg)
Unit Weight
(empty frame)
280 (127)
320 (145�1)
510 (231�3)
540 244�9)
280 (127)
320 (145�1)
Shipping Weight
(empty frame)
320 (145�1)
360 (163�3)
550 (249�5)
580 (263�1)
320 (145�1)
360 (163�3)
Unit Weight
(frame rating populated)
565 (256�3)
700 (317�5)
795 (360�6)
920 (417�3)
565 (256�3)
700 (317�5)
Shipping Weight
(frame rating populated)
605 (274�4)
740 (335�7)
835 (378�7)
960 (435�4)
605 (274�4)
740 (335�7)
Environmental
Operating Temperature
32 - 104°F (0 - 40°C)
Relative Humidity
0 - 95%, non-condensing
Altitude
10,000 ft� @ 77°F) (3000m @ 25°C)
Efficiency (AC-AC), %
91�8-92�0
91�6-92�0
88�5-89�9
88�6-89�7
90�4-91�0
90�0-91�0
Nominal Heat Dissipation
(maximum)
4208 BTU/Hr
5747 BTU/Hr
5528 BTU/Hr
7965 BTU/Hr
4904 BTU/Hr
6768 BTU/Hr
Acoustic Noise Level, dBA
< 55dB (< 50% load), < 65dB (51-100% load) @ 1 meter
Input Data
Nominal Input Voltage,
VAC
200/208/220/230/240; Single-Phase
200/100, 220/110, 230/115,
240/120, 254/127, 208/120,
173/100, 190/110, 200/115,
220/127; Two-Phase
380/400/415; Three-Phase
—
—
Input Voltage Range
The input voltage range based on the output loading, refer to
Table 28
Power Factor, Cos
Single-Phase Input, > 0�99;
Three-phase Input, > 0�95
Single-Phase Input, > 0�99
Input Frequency, Nominal
50/60 Hz
Input Current
Distortion, THDi
< 5%
Input Frequency Range
40 to 70Hz auto-sensing
S5KC SERIES USER MANUAL | 69