3�0 COMMUNICATION
The rear panel of the SolaHD S5KC provides these communication ports:
•
IntelliSlot® ports: 3
•
Dry contact ports: 1
•
REPO (Remote Emergency Power Off): 1
•
Long Run Time (LRT) Battery Temperature Probe Terminals: 1
•
USB port: 1
3.1 IntelliSlot Ports
The three IntelliSlot communication ports (see
Figure 45
) are used for installing communication options, including the
IntelliSlot Unity card, dry contact card, MultiPort and IntelliSlot EBC card� The IntelliSlot ports and the USB port can be
used at the same time�
Figure 45: IntelliSlot communication port location
IntelliSlot Unity Cards — IS-UNITY-DP
•
IS-UNITY-DP
: This optional card can be used instead of the standard card if communication to two third-party
platforms is required� Third-party platforms include SNMP and 485 (Modbus/Bacnet) protocols� This card would
still be used for communication between the SolaHD S5KC UPS and Emerson’s Trellis NMS and LIFE Services� All
communication protocols are active simultaneously�
IntelliSlot® Dry Contact Card (IS-RELAY)
Provides dry contact alarm information, including: On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and
On UPS signals for communication to a remote monitoring system or for use with MultiLink® software� This card also can
accept input signals to shut down the UPS while it is in any mode of operation�
IntelliSlot
Ports
IntelliSlot Ports
(with protective covers)
S5KC SERIES USER MANUAL | 39