Table 22: Item Description of Menu Window and Data Window
(continued)
Menu Name
Data Item
Data Description
Settings (continued)
Communication Address
Sets the UPS device address� This setting is only for the network card
communication of newly emerging market�
Air Filter Reminder
Set the reminder period of checking dust-proof filter
Air Filter Type
Standard: Use this setting if air filter is not installed�
Fine Dust: Use this setting if air filter is installed�
IT System Compatibility
Enabled - Neutral back-feed relay will open on battery mode
Disabled (Default) - Neutral back-feed relay is always closed
UPS ID
Users can set the UPS name to facilitate managing the UPS through remote
communications
Company Name
Set the local service company name of the UPS
Contact Number
Set the local service telephone number of the UPS
Load factory Defaults
Restores the setting items in ‘Settings’ menu to factory values
Battery settings
Low battery Warning
Sets the battery low voltage alarm time
Automatic Battery Test Interval
Sets the interval for the automatic battery test� Intervals of 8, 12, 16, 20, 26
weeks or Disable are available for selection� Factory default is 8 weeks�
Auto Batt Test Start Day
Sets the day of the week for the automatic battery test
Auto Batt Test Start Time
Sets the time of the day for the automatic battery test
External Battery AH
Sets the AH capacity of external third party battery system to calculate the
battery capacity and estimate the battery time remaining
Load Factory Defaults
Restores the setting items in ‘Battery set’ menu to factory values
Language
Language Options
Provides a selection of seven languages:
Chinese, English, French, Spanish, Italian, Russian and German
Alarms
Current Alarms
Displays the current alarms� See Table 25 for the UPS alarm list
Records
Historical Alarms
Displays all historical alarms� See Table 25 for the UPS alarm list
Module replacement
LCD Module
Displays the procedures for replacing LCD module
Bypass Monitor Module
Displays the procedures for replacing system monitor module
Bypass Control Module
Displays the procedures for replacing system control module
Power Module
Displays the procedures for replacing power module
Battery Module
Displays the procedures for replacing battery module
Charger Module
Displays the procedures for replacing charger module
S5KC SERIES USER MANUAL | 49
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]