2.5.3 Transformer-Free UPS—Dual Inverter Frames
A junction box is factory-installed on all models of the SolaHD S5KC to ease cable connection� Select the appropriate
input cables according to Tables 11 and 12 based on the UPS rating and mains frequency� Emerson recommends sizing
the overcurrent protection and wiring for the frame rating for easing upgrades to the UPS system�
To connect the cable:
NOTE
Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box (see
Figure 31
) and pull the cables through them, leaving some slack for
installation�
Figure 39: Knockouts
2. Connect the cables to the corresponding terminal of the power input and output terminals�
3. Tighten the screws to 4�52Nm (40 in-lb) with a 13mm (1/2 in) torque wrench�
Table 11: Input Cable Selection for Transformer-Free Dual Inverter Frames (50/60 Hz)
Maximum
System Rated
Load
Input Voltage – 200/100VAC
Input Voltage – 208/120VAC
Input Voltage – 240/120VAC
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended Input
Protection Circuit
Breaker
5kVA
28A
50A
27A
50A
27A
50A
10kVA
56A
63A
54A
63A
54A
63A
15kVA
84A
100A
80A
100A
80A
100A
20kVA
112A
125A
107A
125A
107A
125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable cross- sectional area is
16mm2 (6AWG); and the rated torque is 4�52Nm (40 in-lb);�
90°C copper wire is recommended�
Table 12: Input cable selection for transformer-free dual inverter frames (50/60 Hz)
Maximum System
Rated Load
Input Voltage – 220/110VAC
Input Voltage – 230/115VAC
Input Voltage – 220/127VAC
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
Maximum
Current in UPS
Mode
Recommended
Input Protection
Circuit Breaker
5kVA
28A
50A
28A
50A
27A
50A
10kVA
56A
63A
56A
63A
54A
63A
15kVA
84A
100A
84A
100A
80A
100A
20kVA
112A
125A
112A
125A
107A
125A
The power input and output terminals accept a maximum cable cross-sectional area of 35mm2 (2AWG); the minimum cable
cross-sectional area is 16mm2 (6AWG); and the rated torque is 4�52Nm (40 in-lb);
90°C copper wire is recommended�
Output Cable Knockout
10-Bay SolaHD S5KC
No Transformer
Input Cable Knockout
Output Cable Knockout
Input Cable Knockout
16-Bay SolaHD S5KC
No Transformer
32 | 2�0