MODULYS Green Power 

- Ref.: IOMMODGPXX01-GB  00

Important

1.1. 

•  This manual contains important instructions for the unit that should be followed during installation and maintenance of the UPS 

and batteries. All safety and operating instructions should be read thoroughly before attempting to wire or operate the unit.

• Keep this manual handy for future consultation.

• The unit must be installed and activated only by qualified technical personnel and authorised by SOCOMEC UPS.

The UPS MUST only be moved by two people at least. The people MUST take position at the sides of the UPS with 
respect to the direction of movement.

•  The unit must remain in a vertical position in all circumstances.

• Connect the PE ground conductor first before you make any other connection.

The UPS mains power supplies (rectifier and bypass) must be protected from voltage transients with devices that 
are suited to the installation; the mains voltage transients must be limited to 2.5 kV. These devices must be sized 
to take into account all the installation parameters (geographical position, whether or not there is a lightning rod, 
whether or not there are other suppressors in the electrical installation, etc.).

•  Install the on-line UPS in a well ventilated area, away from flammable liquids and gases. Do not let the unit come in contact with 

water. 

•  External slits and openings in the cabinet are provided for ventilation. To ensure reliable operation of the product and to protect from 

overheating, these openings must not be blocked or covered. Objects must never be inserted into ventilation holes or openings.

• Do not expose the UPS to rain or liquids in general. Do not introduce external bodies.

•  Do not stand beverage containers on the unit.

•  This UPS was designed to power all modern computer loads and associated peripheral devices, such as monitors, modems, 

cartidge tape drives, external floppy drives and so on. Do not use it for pure inductive or capacitive loads. It is not rated to power 
life support equipment.

•  All repairs or installation should be performed by qualfied service personnel. The UPS contains voltages which are potentially 

hazardous. The output receptacles may be alive even when the UPS is not connected to the mains.

•  Risk of a possible electrocution is possible when the battery is connected to the UPS. Therefore, do not forget to disconnect the 

batteries before any service is to be done on the UPS. To disconnect, remove the battery fuse holder which is located at the rear 
panel of the UPS.

•  Isolate Uninterruptible Power Supply(UPS) before working on the circuit. A readily accessible disconnect device shall be incorpo-

rated in the fixed wiring.

•  If the UPS is not equipped with automatic sectioning against back feed or if the switch is external to the UPS, affix a label bearing 

the following words on all the external switches of the UPS power supply: 

ISOLATE THE UPS BEFORE OPERATING ON THIS CIRCUIT.

•  HIGH LEAKAGE CURRENT – Earth connection essential before connecting power source.

•  The disconnect device shall be a four-pole device and shall disconnect all line conductors and the neutral conductor.

• This equipment conforms to the European Community directives for professional equipment and bears the approval mark 

•  The UPS can be supplied by an IT distribution system with a neutral conductor.

ATTENTION!
Hazardous through electrical shock. Also with disconnection of this unit from the mains, hazardous voltage still 
may be accessible through supply from the batteries. The battery supply should be therefore disconnected in the 
plus and minus pole of the batteries when maintenance or service work inside the UPS is necessary.

• The UPS requires three-phase plus neutral input connections (3P+N).

•  Do not connect the output neutral to ground. The UPS does not modify the neutral arrangements of the system; the use of an 

isolation transformer is required should it be necessary to modify the neutral arrangements downstream of the UPS.

• Before connecting any external battery cabinet, ensure that it is fully compatible with the model of UPS it is to be used with.

• The use of external battery cabinets not supplied by the manufacturers is not recommended.

•  Switch off and isolate the UPS and then wait for 5 minutes before removing the protection panels in order to carry out work on 

parts under dangerous voltage.

•  Do not dispose of the batteries in a fire, the battery may explode.

•  Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.

SAFETY STANDARD

1. 

Summary of Contents for MODULYS Green Power

Page 1: ...ing manual GB Manual de instalaci n y uso ES Manuel d installation et d utilisation FR Manuale di installazione e uso IT Installatie en bedieningshandleiding NL Dokumentacja Techniczno Ruchowa PL Manu...

Page 2: ...ackaging and in the manual in cases of extended storage or UPS inactivity SOCOMEC UPS may at its own discretion opt for the repair of the product or for the replacement of the faulty or defective part...

Page 3: ...Status LED Indicators for Power Module 17 7 MIMIC PANEL 18 7 1 Mimic panel 18 7 2 Meaning of ideograms 19 7 3 Meaning of the luminous bar 19 7 4 LCD display hierachy 20 8 OPERATING PROCEDURES 21 8 1...

Page 4: ...ay be alive even when the UPS is not connected to the mains Risk of a possible electrocution is possible when the battery is connected to the UPS Therefore do not forget to disconnect the batteries be...

Page 5: ...tion of the symbols used on the labels applied to the unit 1 2 All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected DANGER HIGH...

Page 6: ...ure 2 1 1 A space of at least 5 cm must be left between the cabinets see figure 2 1 1 The UPS switches are accessed from the front however a space of at least 1 5 metres should be left at the front of...

Page 7: ...four pole selective S type differentials load leakage currents are added to those generated by the UPS and during transi tory phases power failure and power return short current peaks may occur If lo...

Page 8: ...module 1 CD including the Instalattion and Operating manuals 1 Quick Start Guide 1 SNMP adapter placed in one of two Communication Slots 1 External battery sensor cable Please immediately contact your...

Page 9: ...where the system is installed 1 2 3 4 1 2 3 4 3 4 1 Place the fixture under the bottom of board to enhance the supporting force Please use No 19 wrench to unsvrew the bolts At least three men needed...

Page 10: ...use this may cause damage of UPS or tip over accident 3 Push the UPS from either front or rear side otherwise could cause tip over accident 4 When the UPS needs a long distance movement make use of a...

Page 11: ...EAR VIEWS 4 AUX MAINS Q2 INPUT Q2 OUTPUT Q3 Q4 BY PASS Q5 225A 225A 225A 225A Mimic panel Parallel port Input Dry Contact Output Dry Contact Q3 Output Power connections Q5 By pass Q4 Aux Mains Q1 Inpu...

Page 12: ...it must be possible to make the neutral of the Emergency Mains line electrically common with the neutral of the main input feed line L1 X10 L2 MAINS SUPPLY L3 N1 L11 X40 X20 L21 AUXILIARY MAINS EXT B...

Page 13: ...nstaller s responsibility to check the electrical compatibility and the presence of appropriate protection devices between the UPS and the battery cabinet fuses and switches of sufficient capacity to...

Page 14: ...oth dip switches to ON position The sum of AUX Mains cable length and OUTPUT cable length must be the same for each system This regulation prevents unbalanced load shared by two UPSs under by pass mod...

Page 15: ...sition The sum of AUX Mains cable length and OUTPUT cable length must be the same for each system This regulation prevents unbalanced load shared by two UPSs under by pass mode i e AUX Mains cable 1 O...

Page 16: ...llow the instructions below to replace or install the Power Module in the system WARNING Before removing any Power Module ensure that the remaining Power Modules can support the load CAUTION Power mod...

Page 17: ...nactive When the locking latch is located at and the main power is turned on the power module is failed FLASHING The power module is failed and off line ON The power module is active Note While releas...

Page 18: ...s bar that identifies the condition of the power supply to the load C alphanumeric information that uses a menu layout to provide details on any alarms that may occur and on the measurements controls...

Page 19: ...de alarm Steady General alarm Flashing 17 Periodic maintenance alarm warning Flashing 18 LAN connection ready cable connected Steady Meaning of the luminous bar 7 3 The luminous bar figure 7 1 1 provi...

Page 20: ...D BYPASS ACTIVE ALARMS BYPASS SETTING COMMISSIONING CLEAR STATISTICS INVERTER OUTPUT OUTPUT SETTING SERIAL NUMBER CLEAR LOG INVERTER OUTPUT BATTERY SETTING FW VERSION MAINTENANCE ALARM INVERTER OUTPUT...

Page 21: ...o interruptions or extended black outs the UPS continues to power the load using the energy stored in the battery The mimic panel keeps the user constantly informed on the battery status and on the re...

Page 22: ...breakers are cut off and switched to OFF as well as the breaker or fuse of the external battery cabinet Confirm if the locking latch is located at position in the power module Confirm if the input po...

Page 23: ...wait about 30 seconds and close Q5 BY PASS 3 Switch off Q1 INPUT 4 Switch off Q4 AUX MAINS 5 Switch off Q3 OUTPUT 6 If there is an external battery cabinet switch off the circuit breaker of battery ca...

Page 24: ...Switching onto the manual bypass creates a direct connection between UPS input and output completely excluding the equipment control part This operation is performed in the event of ordinary maintena...

Page 25: ...e While releasing the locking latch of power module during normal mode the power module is off line and discharges the DC bus until the DC bus voltage reaches safety level Then the LED will be off Pow...

Page 26: ...9 2 11 9 2 6 9 2 4 9 2 7 9 2 2 9 2 10 9 2 10 9 2 1 9 2 9 9 2 5 9 2 8 012 DRWMODGP XX 029 DRWMODGP XX 032 DRWMODGP XX 019 DRWMODGP XX 021 DRWMODGP XX 013 DRWMODGP XX 030 DRWMODGP XX 016 DRWMODGP XX 018...

Page 27: ...act Input Two sets The UPS provides two sets of dry contact input to receive external signals and then the UPS can take corresponding response These contacts belong to normal open type P2 1 2 AC GENER...

Page 28: ...e During installation of the parallel redundancy the parallel communication is abnormal Output overload warning shutdown The loading is over rated output of the UPS Power module fault shutdown The mod...

Page 29: ...packet to wake up PC Send the e mail and SNMP trap to notify users Provides JNC software to protect public operating systems Provides the InsightPower EzSetting software to easily configure for the f...

Page 30: ...80 A phase EMERGENCY OFF E P O Remote E P O ON OUTPUT BREAKER OFF Output breaker not turn on BYP OVERLOAD WARNING 104 overload when UPS is on bypass BAT CABINET OVER HEAT Battery cabinet over 35 C EXT...

Page 31: ...r maximum performance Furthermore during the operating life of the battery Modulys green power stores statistics on the conditions of use of the battery for analysis Since the expected life of the bat...

Page 32: ...20 Power 3 kW 18 Battery charging current A 1 2 5 Efficiency on line mode up to 96 Efficiency eco mode up to 98 Weight kg 30 Environment Operating temperture C 0 to 40 15 to 25 for best battery life S...

Page 33: ......

Page 34: ...ness Park Broadway Lane South Cerney Cirencester GL7 5XL Tel 44 0 1285 863300 info ups uk socomec com OTHER COUNTRIES Tel 34 935 407 575 info ups europe socomec com IN EASTERN EUROPE MIDDLE EAST AFRIC...

Reviews: