10.
Input Dry Contact
10.1.
P1 - REPO (Remote Emergency Power OFF)
It provides a convenient method for users remotely power off the UPS if an emergency event occurs. Simply connect the cable from
remote site to this terminal. The user may install a switch to easily power off the UPS. This REPO is a normal open contact.
P1
External contact
1
2
P2 - Dry Contact Input (Two sets)
The UPS provides two sets of dry contact input to receive external signals and then the UPS can take corresponding response.
These contacts belong to “normal open” type:
• P2 (1,2) - AC GENERATOR FUNCTION: limit the charger current (3 A) when using generator source
• P2 (3,4) - REMOTE SHUTDOWN FUNCTION: available in Normal Mode and Battery Mode. The UPS switches off after 1 minute.
P3-P4-P5-P6 - External Battery Cabinet Temperature
Available as standard, the “sensor kit” allows to detect the temperature of external battery cabinet.
P7 - Reserved
Slots for optional communication cards
Parallel port
Output Dry Contact
Input Dry Contact
10-1
Communication interfaces