12
MODULYS Green Power
- Ref.: IOMMODGPXX01-GB 00
CONNECTIONS
5.
L1
X10
L2
MAINS SUPPLY
L3
N1
L11
X40
X20
L21
AUXILIARY MAINS
EXT BATTERY
L31
N11
N
240V DC
240V DC
L12
X50
L22
OUTPUT
L32
N2
5.1-1
Mains and Aux Mains connected separately
5.1.
The UPS must not operate without the neutral connection to the input.
For equipment with separate Emergency Mains, it must be possible to make the neutral of the Emergency Mains
line electrically common with the neutral of the main input feed line.
L1
X10
L2
MAINS SUPPLY
L3
N1
L11
X40
X20
L21
AUXILIARY MAINS
EXT BATTERY
L31
N11
N
240V DC
240V DC
L12
X50
L22
OUTPUT
L32
N2
5.2-1
Mains and Aux Mains connected in common
5.2.
Cable specifications:
• stripping lenth: 20 mm
• tightening torque: 10 Nm
WARNING!
In case of a generator connection or unstable Auxiliary Mains,
only the common connection can be used.
MAINS
MAINS
LOAD
LOAD
AUX MAINS
006 DR
WMODGP-XX
007 DR
WMODGP-XX
Summary of Contents for MODULYS Green Power