22
MODULYS Green Power
- Ref.: IOMMODGPXX01-GB 00
8. OPERATING PROCEDURES
Commissioning
8.5.
During activation of the equipment a warranty activation code, made up of four characters, is requested to complete the start-up
procedure. The activation code is provided directly by the reference Support Centre upon communication of the serial number of
the equipment which is displayed in the message at first start procedure.
SEE INSTALLATION MANUAL
FOR PROCEDURE
SN: 0000000000
When contact is made with the Support Centre for the activation code, detailed information can be obtained on the UPS functions
available and on the periodic preventive maintenance programmes. Once the code is obtained, enter it by pressing ENTER to acti-
vate the entry. Select the first character with the UP
and DOWN
keys and confirm with ENTER to accept the character. Then
move on to the next character. Pressing the ENTER key after selecting the fourth character activates code.
SEE INSTALLATION MANUAL
FOR PROCEDURE
CODE = A A A A
An error message is displayed if the code is incorrect. Check that the code displayed corresponds to the one provided by the
Support Centre and repeat the procedure.
Single Unit (up to 120 kVA)
8.6.
Startup Procedures
8.6.1.
Before starting up the UPS system, be sure to check the following items first.
• Ensure all circuit breakers are cut off and switched to OFF, as well as the breaker or fuse of the external battery cabinet.
• Confirm if the locking latch is located at position in the power module.
• Confirm if the input power source matches the rated voltage, frequency, phase and battery of the UPS that you have installed.
If the conditions mentioned above are satisfied, follow the steps below to start up.
1. If there is an external battery cabinet, switch the circuit breaker of battery cabinet to ON and confirm if manual bypass protection
circuit breaker Q5 (BY-PASS) is cut off and switched to OFF.
2. Switch on Q1 (INPUT), Q4 (AUX MAINS) and Q3 (OUTPUT). The LCD monitor will start displaying. After initialization, the LCD
screen will show ”LOAD NOT SUPPLIED”.
3. Press the “ON” button for 3 seconds until you hear a “beep” and then release the button.
4. At this time, the LCD screen will show "SELF DIAGNOSIS" and after 30 seconds the load is powered by the UPS.
Battery Startup Procedures
8.6.2.
1. Switch the circuit breaker of external battery cabinet to ON and confirm if Q5 (BY-PASS) is cut off and switched to OFF.
2. Switch on Q3 (OUTPUT).
3. Press the “ON” button for 3 seconds until you hear a “beep” and then release the button. The LCD screen will show "SELF
DIAGNOSIS".
4. The UPS will start up by DC-bus soft start. The inverter will be activated by adopting the default frequency value.
5. When the inverter startup is completed, the UPS will transfer to Inverter mode and the luminous bar turns to yellow colour.
6. The load is powered by the ups in battery mode.
Summary of Contents for MODULYS Green Power
Page 33: ......