Output Dry Contact
10.2.
1
2
3
4
5
6
7
8
9
10
11
12
The UPS provides 6 dry contact outputs that can be set to normally open or normally close via SNMP web card. The default contact
position is NO. The default message is shown in the tables below. NO or NC contacts admitted nominal current: 2 A 250 VAC
Contact
Message
Description
1-2
Input backfeed
Input backfeed is activated
3-4
Bypass backfeed
Bypass backfeed is activated
5-6
Load on Battery
The UPS is on Battery mode
7-8
Battery Low
The UPS is on Battery mode and the battery voltage is closed to the lower
limit (battery voltage < 220 V)
9-10
Load on auto by-pass
The UPS is in bypass mode
11-12
General Alarm
At least one active alarm is present
Contacts 5-6, 7-8, 9-10, 11-12 can also be settable via SNMP web card for monitoring the following UPS status.
Message
Description
Internal communication failure
The communication of module is abnormal.
External parallel communication failure
During installation of the parallel redundancy, the parallel communication is
abnormal.
Output overload warning/shutdown
The loading is over rated output of the UPS.
Power module fault shutdown
The module fails and the UPS is shut down.
Power module warning
The module has errors, but the UPS can still function normally.
EPO activated
Urgently power off the UPS.
Load on manual bypass
The UPS transfers to manual bypass mode.
Battery cabinet over temperature warning/shut-
down
The temperature is too high.
Output voltage abnormal
The output voltage is too high or too low.
Battery need replace
Overdue for battery replacement (Compared with system setup.)
Bypass over temperature warning/shutdown
Bypass “static transfer switch” is over temperature.
Battery ground fault
Grounding error
Bypass static switch fault
The bypass “static transfer switch” is abnormal.
Parallel port
10.3.
For redundancy or for increasing the power, two UPSs can be installed via a parallel communication cable.
Use the parallel communication cable provided in the accessory pack.
Linking the UPS with other cables will result in accidents.
Both dip-switches has to be set to ON.
10. COMMUNICATION INTERFACE
043 DR
WMODGP-XX