- 39 –
No.JXC
※
-OMY0002
Setting name
Range
Description
Trigger LV
Minimum value
to "Max force"
of the basic
parameter
*1)
●Effective only for the pushing operation (when the value for the
"Pushing force" is from 1 to 100).
This is the setting to define the conditions where the INP will be turned
ON. When the electric actuator generates a force over this value, INP
will be turned ON. (Unit: %)
●For the positioning operation, this value is ignored.
Pushing speed
Minimum value
to "Max force"
of the basic
parameter
*1)
●Effective only for the pushing operation (when the value for the
"Pushing force" is from 1to 100).
This defines the movement speed during the pushing operation. If
this Speed is too high, it may cause damage to the electric actuator
or work piece due to impacts. Therefore, enter a value within the
range appropriate for the electric actuator. (Unit: mm/s)
Please refer to the electric actuator manual for the appropriate range
of the speed.
●For the positioning operation, this value is ignored.
Moving force
*1)
The setting to define the maximum torque during the positioning
operation.
Enter a value within the range appropriate for the electric actuator.
(Unit: %).
Please refer to the electric actuator manual for the appropriate range
of the speed.
Area1
"Stroke (-)" to
"Area2" of step
data
The setting to define the conditions where the AREA output will be
turned ON (Unit: mm).
If the current position is within the range between the Area1 and
Area2, the AREA output will be turned ON.
If Area1 >Area2, the alarm "Step Data ALM1" will be activated.
(However, no alarm is generated if "Area1" = "Area2" = 0, the AREA
output will be turned OFF).
Area2
"Area1" of step
data to "Stroke
(+)" of the
basic
parameter
In position
*1)
The functions of this will be different between the pushing operation
and the positioning operation.
●Positioning operation: Positioning range (Unit: mm).
●Pushing operation: Pushing distance (Unit: mm).
Operation
Description
Positioning
operation
This is the setting to define the conditions where the
INP output will be turned ON.
When the electric actuator enters within this range
from the target position, the INP will be turned ON.
(It is unnecessary to change this from the initial
value.)
If it is required to get a signal before the electric
actuator completes the positioning operation, this
value should be larger.
The INP output will be turned on. Target position -
in position
≦
electric actuator position
≦
target
po in position
Pushing
operation
This is the setting to define the distance pushed by
the electric actuator during the pushing operation.
When the electric actuator pushed exceeding this
distance, the pushing operation will end.
In case of such stop exceeding the pushing
distance, the INP will not be turned ON.
*1) The range varies depending on the electric actuator.
Please refer to the manual of the electric actuator for more details.