HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.1
Function
5-5
Table 5.1-2 List of parameter (2/3)
Display
Content
Default setting
∗
4
Reference
page
Category
Changing of pump operation mode
PRS
Circulating fluid outlet pressure
0.50MPa (72.0PSI)
(----)
∗
5
Pump operation frequency
---- (30)
∗
5
5.16
Warming up function
OFF
Warming up temperature setting
----
(20.0
o
C (68.0
゚
F)
∗
6
5.17
Anti-snow coverage function
OFF 5.18
Dust-proof filter accumulated time reset
NO 5.15
Setting
menu
Alarm buzzer sound
ON
5.19
Changing of low tank level
A.STP
Changing of circulating fluid discharge
temperature rise
A.RUN
Detection temperature for circulating fluid
discharge temperature rise
40.0
o
C (104.0
゚
F)
(----)
∗
7
Changing of circulating fluid discharge
temperature drop
A.RUN
Detection temperature for circulating fluid
discharge temperature drop
1.0
o
C (33.8
゚
F)
(----)
∗
7
Changing of circulating fluid discharge
pressure rise
A.STP
Detection pressure for circulating fluid
discharge pressure rise
1.00MPa (145PSI)
(----)
∗
7
Changing of circulating fluid discharge
pressure drop
A.STP
Detection pressure for circulating fluid
discharge pressure drop
0.05MPa (7PSI)
(----)
∗
7
Changing of communication error
OFF
The monitoring time of communication error
---- (30)
∗
7
Changing of Contact input signal 1
detection
A.STP
Changing of Contact input signal 2
detection
A.STP
Changing of DC line fuse cut
A.STP
Unused
----
Unused
----
Unused
----
Unused
----
Unused
----
Temperature alarm monitoring method
0
Monitoring start timer
---- (0)
∗
7
Range over
Detection timer
5
Compressor stop alarm
P.RUN
5.20
Alarm setting
menu
∗4
: Values in
゚
F are displayed when SE12 is F and PSI are displayed when SE13 is PSI.
∗
5: The default setting when SE24 is FREQ.
∗
6: The default setting when SE27 is ON.
∗
7: Regarding the detail of the default setting, refer to “5.20
Alarm customizing function
”.