HRX-OM-Q026-B
Chapter 5 Display and setting of various functions
HRSH Series
5.20
Alarm customizing function
5-47
Table 5.20-2 Alarm setting and customizing (2/4)
①
Alarm operations
②
Alarm threshold and others
∗4
Code
Alarm name
Display
A.STP
A.R
UN
P.RUN
OFF
Display
Default
setting
Settable range
Set temperature
1.0
℃
(33.8
゚
F)
(----)
∗
5
1.0
~
34.0
℃
(33.8
~
93.2
゚
F)
Monitoring method
0
0
~
3
Monitoring start timer
----
(
0
)
∗
6
0 to 600 minutes
Range over detection timer
AL04
Circulating fluid
discharge temp.
drop
●
○
-
●
5 5
to
999
seconds
AL05
High circulating
return temp.
-
○
-
-
-
-
-
Set pressure
AL08
Circulating fluid
discharge
pressure rise
○
●
-
●
1.00MPa
(145PSI)
(----)
∗
7
0.05 to 1.00MPa
(7
~
145PSI)
Set pressure
AL09
Circulating fluid
discharge
pressure drop
○
●
-
●
0.05MPa
(7PSI)
(----)
∗
8
0.05 to 1.00MPa
(7 to 145PSI)
AL10
High compressor
suction temp.
●
-
○
-
-
-
AL11
Low compressor
suction temp.
●
-
○
-
-
-
AL12
Low super heat
temperature
●
-
○
-
-
-
AL13
High compressor
discharge
pressure
●
-
○
-
-
-
AL15
Refrigerant circuit
pressure (high
pressure side)
drop
●
-
○
-
-
-
AL16
Refrigerant circuit
pressure (low
pressure side)
rise
●
-
○
-
-
-
∗
4: Values in
゚
F are displayed when SE12 is F, and PSI are displayed when SE13 is PSI.
∗
5: The default setting when AS05 is OFF.
∗
6: The default setting when AS21 is 2 or 3.
∗
7: The default setting when AS07 is OFF.
∗
8: The default setting when AS09 is OFF.