HRX-OM-Q026-B
Chapter 8 Documents
HRSH Series
8.1 Specifications
8-1
Chapter 8 Documents
8.1 Specifications
8.1.1 HRSH150/200/250-A
∗
-20-
∗
Table 8-1 Specifications [HRS150/200/250-A
∗
-20-
∗
]
Model
HRSH150-A
∗
-20-
∗
HRSH200-A
∗
-20-
∗
HRSH250-A
∗
-20-
∗
Cooling method
Air-cooled refrigerated type
Refrigerant R410A
(HFC)
Control method
PIDcontrol
Ambient temperature
∗
1
Temperature
:
5 to 45
o
C
Circulating fluid
∗
2
Tap water, Ethylene glycol aqueous solution 15%
Operating temperature range
∗
1
o
C
5 to 35
Cooling capacity
∗
3
kW
15.7
20.5
25
Heating capacity
∗
4
kW
3
5.5
7.5
±1.0
Temperature stability
o
C
±0.1(Stable heat load, Rated flow rate, Power supply AC200V)
Rated flow rate
(Outlet)
L/min
43 (0.47MPa)
125 (0.5MPa)
Maximum flow rate
L/min
130 180
Pump
capacity
Maximum lifting
height
m 50
80
Settable pressure range
∗
5
MPa
0.1 to 0.5
0.1 to 0.8
Minimum operating flow rate
∗
6
L/min
25
40
Tank capacity
L
42
60
Circulating fluid outlet, circulating fluid
return port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Tank drain port
Rc3/4 (Symbol F: G3/4, Symbol N: NPT3/4)
Supply side
press. range
MPa
0.2 to 0.5
Supply side
fluid temp.
o
C
5 to 35
Automatic fluid fill port
Rc1/2 (Symbol F: G1/2, Symbol N: NPT3/4)
Automatic
fluid fill
system
(Standard)
Over flow port
Rc1 (Symbol F: G1, Symbol N: NPT1)
Circulating
fluid
system
Wetted material
SUS, Cu(Heat exchanger
’
s brazing ), PTFE,
PU, FKM, EPDM, PVC, NBR, POM
、
PE
、
NR, BS (Y strainer)
Power supply
AC200/200-230V 50/60Hz 3phase
Allowable voltage fluctuation ±10% (No continuous voltage fluctuation)
Rated
current
A
30 40 50
Recommended
earth leakage
breaker
∗
7
Sensitivity mA
30
Rated operating current
∗
8
A
17 25 34
Electric
system
Rated power consumption
∗
8
kW (kVA)
5.8 (6)
8.4 (8.7)
10.4 (11.6)
Sound level (F
ront 1m/Height 1m)
dB(A)
62
66
Water-proof specification
IPX4
Accessory
Alarm cord list label 2pc.(English 1pc./Japanese 1pc.), Operation
manual 2pc. (English 1pc./Japanese 1pc.),
Y strainer (40 meshes) 25A, Barrel nipple 25A
Weight
(dry condition)
kg
Approx.215
Applox. 280
∗
1 Use a 15% ethylene glycol aqueous solution if operating in a place where the circulating fluid temp. or ambient temperature is lower
than 10
o
C
∗
2 Use fluid in condition below as the circulating fluid.
Tap water: Standard of The Japan Refregeration And Air Conditioning Industry Association (JRA GL-02-1994)
15% ethylene glycol aqueous solution: diluted by tap water in condition above without any additives such as antiseptics.
Deionized wate: Conductivity 1
μ
S/cm and higher (electrical resistivity 1M
Ω・
cm and lower)
∗
3 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Criculating fluid flow rate :
Rated flow rate, (5)Power supply: AC200V
∗
4 (1)Operating ambient temp.: 32
o
C, (2)Circulating fluid : Tap water, (3) Criculating fluid flow rate : Rated flow rate, (4)Power supply:
AC200V
∗
5
With the pressure control mode of the pump operation mode. When the pressure control mode is not necessary, use the fequency
set mode
∗
6
Fluid flow rate to maintain the cooling capacity and the temperature stability. If the actual flow rate is lower than this, please install
a bypass piping.
∗
7
To be prepared by the customer. A specified earth leakage breaker is installed for option B [Earth leakage breaker] of each model.
∗
8 (1)Operating ambient temp.: 32
o
C, (2)Criculating fluid : Tap water, (3)Circulating fluid temp.: 20
o
C, (4)Heat load : Same as the
cooling capacity, (5)Circulating fluid flow rate: Rated flow rate, (6)Power : AC200V