HRX-OM-Q026-B
Chapter 4 Starting the Product
HRSH Series
4.5
Check items after starting
4-9
4.5 Check items after starting
Check the following items after starting the product.
z
There is no leakage from piping.
z
There is no drain of circulating fluid from the tank drain port.
z
The circulating fluid pressure is within the specified range.
z
The tank level is within the specified range.
4.6 Adjustment of Circulating Fluid flow rate
Circulating fluid flow rate adjustment
If the flow rate is lower than HRSH150/200
:
25L/min, HRSH250
:
40L/min,
the performances may not be able to achieve the specified ones and the
compressor may not start running.
Adjust the hand valve installed by the customer side referring to
Fig. 3-16
Recommended piping circuit
to make the desired pressure or/and flow rate.
When an Alarm is seen, press the [STOP] button and then turn off the
breaker to stop the product, and turn off the breaker of the user’s
power supply to isolate the product.