The specific data of SG actuators are shown in the table:
Parameter
Actuator type*
SG16..
SG20..
SG26..
SG40..
SG60..
SG80..
SG100.. SG120..
Supply voltage
24 V DC
Current consumption when
operating without load
0.8 A
Ambient temperature range
–25 °C to +60 °C
Maximum acceptable
temperature according to
EN 12101-2, Appendix G
300
°C – 30 min
Ingress Protection Rating
according to
DIN EN 60529
IP 54
Current consumption at full
load [A]
1.6
2.0
2.6
4.0
6.0
8.0
10.0
12.0
Speed without load [mm/s]
6.2-20.8 6.2-20.8 6.2-20.8 6.7-36.7 21.9-36.8 30.3-36.8 17.1-25.6 17.1-25.6
Speed at full load [mm/s]
5.1-17.2 4.8-16.3 4.4-14.9 5.3-29.2 15.2-25.6 18.1-22.0 12.7-19.0 11.7-17.6
Operating mode at peak
load, at 250C
S2 4
S2 2.5
S2 1.5
S2 4
S2 2
S2 1
S2 2
S2 2
Operating mode at
continuous load, at 400C
S3 21% S3 13%
S3 8%
S3 20% S3 10%
S3 5%
Maximum activation time of
the actuator in one
direction [min]
4
2.5
1.5
4
2
1
Ingress Protection Rating of the housing: IP 54
Operating temperature: -250C to +600C
Other important technical data concerning actuators are available on individual request.
Wiring diagrams:
Rys. 42. Connecting diagram.
Technical conditions for SG actuators installation.
•
Mechanical installation of SG actuator consists of mounting the actuator to the
drive console and connecting the actuator eye bolt with a MHV hook lock. It is very
important to adjust this connection. The proper adjustment ensures reliable
latching of the MHV lock on a T fitting, and at the same time turning the actuator
off by the limit switch, not the overload switch.
Connecting diagram with E option (potential-free contacts)
contact cable
1
brown
2
blue
contact cable
1
1
2
2
3
3
4
brown
5
blue
b
lu
e
b
ro
w
n
b
lu
e
b
ro
w
n
blue
brown
blue
brown
pull out
slip in
General
Standard version
close
open
contacts shown in the position (piston rod pulled in)