Operation and Maintenance Manual
– SCD Smoke Dampers
Version 1
Date 04 2018
Page 40 of 81
Technical Data:
Maximum static operating pressure
80 bar
Maximum dynamic operating pressure
80 bar
Valve nominal diameter
2 mm
Pin nominal diameter
2 mm
Operating temperature range
-250
°C to +1100 °C
In systems carrying out the “A” “open only” operating mode, TAVE thermal trips are
used.
Channels marking:
VA
-
“Open” input
CA
-
“Open” output
Rys. 19. TAVE thermal trip
Types of TAVE thermal trips:
Type
Vent valve
A Cylinder thread
TAVE 3.01
no
1/2" UNF (standard)
TAVE 3.01-M
no
M18 x 1.5
TAVE 3.01-F
no
W21.8 x 1/14"
TAVE 3.11
yes
1/2" UNF (standard)
TAVE 3.11-M
yes
M18 x 1.5
TAVE 3.11-F
yes
W21.8 x 1/14"
VA input in standby mode (the valve enabled
–disabled) is connected with the CA
output, which makes it possible, among other things, to carry out the damper ventilation
function without any interruption. Option with venting:
CA output in standby mode is vented by means of an integrated drain (vent) valve.
After pressurising VA input (from the alarm or ventilation box), connection between VA
input and CA output is set up.
Installation:
1. Make the following connections:
CA
– OPEN side of the actuator
VA
– OPEN ventilation or smoke extraction circuit
C
CA
VA