HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 11 of 44
CAUTION!
Default password is 00318. Users can change it in case others change the advanced parameter settings.
Please clearly remember the password after changing. If you forget it, please contact SmartGen services and feedback
PD information in controller
ABOUT
page to us.
4.3 LCD DISPLAY
4.3.1 MAIN DISPLAY
Main screen is displayed by pagination.
is used to scroll the pages and
is to scroll the
screens.
Main Screen
includes the following:
A part of statuses
Bus: voltage, frequency, active power, reactive power
Mains: voltage, frequency, current, active power, reactive power
NOTE:
Main screens will circularly display if there is not scroll operation.
Status
includes the following: Genset status, switch status, mains status;
Mains
includes the following:
Phase voltage, wire voltage, frequency, phase sequence, each phase current, each phase and total
active power (positive and negative), each phase and total reactive power (positive and negative), each
phase and total apparent power, each phase and average power factors (positive and negative), total
electric energy, ground current, imbalance current, total electric energy of user A and B.
NOTE:
Power factor display illustration:
NOTE:
P stands for active power;
Q stands for inactive power.
Table 6 Power Factor Illustration
Power factor Conditions Active power Reactive power
Remark
COS>0L
P>0,Q>0
Input
Input
Load is resistor-inductance;
COS>0C
P>0,Q<0
Input
Output
Load is resistor-capacitance.
COS<0L
P<0,Q>0
Output
Input
Load is equal to an under excitation generator.
COS<0C
P<0,Q<0
Output
Output
Load is equal to an over excitation generator.
NOTE:
1. Input active power, genset or mains sends active power to load.
2. Output active power, load supplies power to generator or mains.
3. Input reactive power, generator or mains sends reactive power to load.
4. Output reactive power, load sends reactive power to generator or mains.