HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 28 of 44
No.
Items
Range
Defaults
Description
25
Sync Control Gain
(0-500)%
20
Regulate and control before parallel;
26
Sync
Control
Stability
(0-2000)%
20
Regulate and control before parallel;
27
Reactive
Power
Control Gain
(0-500)%
20
Regulate and control after parallel;
28
Reactive
Power
Control Stability
(0-2000)%
20
Regulate and control after parallel;
8.2 DEFINABLE CONTENTS OF PROGRAMMABLE OUTUT PORTS
Table 14 Definable Contents of Programmable Output Ports
No.
Type
Description
0
Not Used
1-6
Reserved
7
Custom Combined 1
For details of function description please see the following
contents.
8
Custom Combined 2
9
Custom Combined 3
10
Custom Combined 4
11
Custom Combined 5
12
Custom Combined 6
13-17
Reserved
18
Audible Alarm
Act at warning, shutdown, and trips; Can connect an
announciator externally; When
“alarm mute” configurable input
port is active, it is prohibited to output;
19-25
Reserved
26
Remote Control Output
This port is controlled by communication (PC).
27-28
Reserved
29
Bus Close Output
Control bus to take load.
30
Bus Open Output
Control bus to unload.
31
Mains Close Output
Control mains to take load.
32
Mains Open Output
Control mains to unload;
33-43
Reserved
44
Bus OK
Act when bus voltage is normal.
45
Reserved
46
Mains normal output
47
Synchronizing
48
Common Alarm
Act at genset common warning, common shutdown, common
trip alarms.
49
Common Trip and Stop
Act at common trip and stop alarms.
50
Common Shutdown
Act at common shutdown alarms.
51
Common Trip
Act at common trip alarms without stop.
52
Common Warning
Act at common warning alarms.