HGM8156 GENSET PARALLEL CONTROLLER USER MANUAL
HGM8156 Genset Parallel (With Mains) Controller 2019-09-10 Version 1.1 Page 22 of 44
No.
Items
Range
Defaults
Description
15
Over Voltage
(0-200)%
105
Rated voltage percentage; alarm action
(default: trip and stop) and delay value
(default: 0.1s) can also be set;
16
Under Voltage
(0-200)%
95
17
Over Frequency
(0-200)%
105
Rated frequency percentage; alarm action
(default: trip and stop) and delay value
(default: 0.1s) can also be set;
18
Under Frequency
(0-200)%
95
19
ROCOF
(0-1.00)Hz/s
0.20
Set value is ROCOF; alarm action (default:
trip and stop) and delay value (default: 0.1s)
can also be set;
20
VECTOR
(0-20.0)°
6.0
Set value is Vector Shift; alarm action
(default: trip and stop) and delay value
(default: 0.1s) can also be set;
Timer Setting
1
Start Delay
(0~3600)s
5
Time from remote start signal is active to
genset start.
2
Stop Delay
(0~3600)s
30
Time from remote start signal is inactive to
genset stop.
Battery Setting
1
Rated Voltage
(0-60.0)V
24.0
Provide standard for battery under/over
voltage detection.
2
Over Voltage Warn
(0-200)%
120
Rated voltage percentage; return value (over
voltage return value default: 115, under
voltage return value default: 90) and delay
value (default: 60s) can also be set.
3
Under Voltage Warn (0-200)%
85
Bus Setting
1
AC System
(0~3)
0
0: 3P4W;
1: 3P3W;
2: 2P3W;
3: 1P2W.
2
Rated Voltage
(30~30000)V
230
If PT is fitted, it is also primary voltage when
voltage transformer is used.
3
Rated Frequency
(10.0-75.0)Hz
50.0
Standards
for
detecting
over/under
frequency.
4
Volt. Trans.(PT)
(0~1)
0
0: Disable;
1:Enable
5
Full-load
Active
Power
(1-60000)kW
276
Active power of bus full load, used for load
share;
6
Full-load
Inactive
Power
(1-60000)kVar
210
Reactive power of bus full load, used for
load share;
7
Load Ramp
(0.1-100.0)%
3.0
Load/unload rate %/s
8
Ramp Delay Point
(0.1-40.0)%
10.0
Each time load value is added by this point,
after this delay it will continue loading.
9
Ramp Delay
(0-30)s
0